Troubleshooting guide – Reznor VPT Unit Installation Manual User Manual
Page 35

35
6. Troubleshooting Guide.
START
Ensure gas & electricity
supplies are enabled.
Turn any external timer
to call for heat (if fitted).
Does the Power On
light illuminate?
NO
YES
Set two-stage thermostat to
call for heat at maximum
setting (High Fire).
NO
YES
CHECK: -
1. Operation of any timer or control.
2. External fuses.
3. Supply Voltage is 120VAC 60Hz
Is there power to the
burner?
CHECK: -
1. Transformer
2. Integrity of wiring connections.
3. Light.
Does the fan run?
NO
YES
CHECK: -
1. Voltage supply to fan terminal F2(F1on low fire is 120VAC 60Hz
2. Integrity of wiring connections.
3. Fan.
Do the amber
lights illuminate after a
purge period?
NO
Is there power to
the fan?
YES
NO
CHECK: -
1. Relays is correctly fitted
2. Voltage across terminals A1 & A2 is 24VAC/60Hz(when calling for high fire).
3. Integrity of wiring connections.
4. Pressure switch operation.
5. Ignition controller.
6. Transformer.
Does the Pressure
switch close?
YES
NO
CHECK: -
1. Pressure switch wiring connections.
4. Integrity of wiring connections.
5. Amber lights.
6. Ignition controller.
5. Transformer
CHECK: -
1. Hose connection to vacuum switch.
2. Air inlet, outlet, and emitter tubes for obstructions.
3. Pressure switch operation.
4. Supply voltage 120VAC / 60Hz
5. Transformer.
6. Ignition Controller.
YES