Appendix C: Module Specifi cations And Features

PFC-5002 Fire Alarm Control Panel

General

Two supervised Class B (Style B) or one Class A (Style D)
Initiating circuits; confi gurable (normal or verifi ed, and for
Class B there may be one waterfl ow and one supervisory).
[Compatibility ID “A”]

Two Class A/B (Style Y/Z) NAC circuits; confi gurable as
strobes or audibles.
Power limited: 24 VDC unfi ltered

1.7 A per circuit (2.0 a total)

Initiating circuit disconnect switch.

Optional UDACT or city tie adder module.

Optional ARM-4 / ARM-8 Relay Module.

Resettable four-wire smoke supply.
Power Limited: 28VDC, 100mA max, 1.5Vp-p ripple

Aux power supply.
Power limited: 24VDC, 300mA max, special application for
RTI or remote annunciators.

1 RTI Interface for connection to an RTI Remote Trouble
Indicator.

Auxiliary relays (resistive loads):
Common Alarm: Form C, 1Amp, 28VDC
Common Trouble:Form C, 1Amp, 28VDC

DIP switch confi gurable.

Walktest function.

Electrical ratings

AC Line Voltage: 120V 0.74A 60Hz / 240V 0.34A 50/60Hz

Two amps (inline fuse on transformer primary)

Power supply ratings: 2.4 amps. max. (secondary)

For NAC circuits: 24VDC unfi ltered 2.0 amps. max.

Battery: 24VDC, gel-cell/sealed lead-acid

Charging capability: 4 to 24 AHr batteries
(cabinet will hold up to 8AH)

Current consumption: standby: 110 mA / alarm: 220 mA

PFC-5004E/PFC-5008 Fire Alarm Control Panel

General

Four supervised Style B (Class B) or 2 Style D (Class A)
initiating circuits; confi gurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA
max. (alarm)

Two Class A/B (Style Y/ Z) NAC circuits; confi gurable as
strobes or audibles.
Power limited:24 VDC unfi ltered

1.7 A per circuit (5A total)

One ZA-42 Zone Adder Module may be added.

Initiating circuit disconnect switches.

Optional DACT or city tie adder module.

Optional ARM-4 / ARM-8 Relay Module.

Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple

Aux power supply.

Power limited: 24VDC, 300mA max, special application

for RTI or Remote Annunciators

1 RS-485 connection for up to 3 RA8F Remote Annunciators.

1 RTI interface for connection to an RTI Remote Trouble Indicator.

Auxiliary relays (resistive loads):

Common Alarm: Form C, 1Amp, 28VDC
Common Trouble: Form C, 1Amp, 28VDC

Common Supervisory: Form C, 1Amp, 28VDC

DIP switch confi gurable.

Walktest function.

Electrical ratings:

AC Line Voltage:120V 1.65A 60Hz / 240V 0.64A 50/60Hz

Power supply ratings: 6 amps max. (secondary)

For NAC circuits: 24VDC unfi ltered, 5 amps max.

Battery: 24VDC, Gel-Cell/Sealed Lead-Acid

Charging capability: 4 to 24 AH batteries

(cabinet will hold up to 12AH)

Current consumption: standby: 110 mA / alarm: 220 mA

PFC-5004 Fire Alarm Control Panel

Same as PFC-5002, except ...

Only has four supervised Class B (Style B) or two Class A (Style
D) initiating circuits; confi gurable (normal or verifi ed).
[Compatibility ID “A”]

Zone 3 confi gurable as Waterfl ow

Zone 4 confi gurable as Supervisory