beautypg.com

Potter PFC-5000 Series User Manual

Page 14

background image

10

Zone Adder Module (Model ZA-42)

Figure 6: ZA-42 Zone Adder Module

Class A / B Selection: JW2 & JW3 are connected from 1 to 2 for initiating circuit Class B (Style B) operation, and from 2 to 3
for Class A (Style D) operation.

Note:
The Class A/B selection affects all initiating circuits, and must be used with the correct Confi guration DIP switch 9 #6.

P1 & P2: Connections to P7 & P6 respectively on the main fi re alarm board.

SW5,6: Confi g DIP switches.

P1

S

L

A

NI

M

R

E

T

G

NI

RI
W

D

L

EI

F

P2

SW5

2 3

1

JW3

SW6

2 3

1

JW2

A LM

K1

RLY1

RM

-208

/

R

M

-20

4

RE

L

A

Y

MO

D

UL

E

RLY2

RLY3

RLY4

RLY5

RLY6

RLY7

RLY8

NO

NO

NC

CO

M

NO

NC

CO

M

NO

NC

CO

M

CO

M

NO

NC

CO

M

NO

NC

CO

M

NO

NC

NC

CO

M

NO

NC

CO

M

K2

K3

K4

K5

K6

K7

K8

JW

1A

SUPV

JW 1

JW 2

JW 3

JW 4

P1

JW 5

JW 6

JW 7

JW 8

JW1.2

A LM

JW

2

A

SUPV

JW2.3

A LM

JW

3

A

SUPV

JW 3.4

A LM

JW

4

A

SUPV

JW4.5

A LM

JW

5

A

SUPV

JW5.6

A LM

JW

6

A

SUPV

JW6.7

A LM

JW

7

A

SUPV

A LM

JW

8

A

SUPV

JW7.8

Relay Modules (Models ARM-4 or ARM-8)

Figure 7: ARM-4 or ARM-8 Relay Adder Module (Zone Operated)

P1: Connect to P1 on the main fi re alarm board.

By the factory setting, the four or eight relays are controlled by initiating circuits 1 to 8 respectively. This is confi gured by
selecting:

JW1:

Initiating Circuit #1 controls Relay #1.

JW2

: Initiating Circuit #2 controls Relay #2.

JW8:

Initiating Circuit #8 controls Relay #8.

Alternately, each relay may be set as a Common Alarm or Common Supervisory Relay by removing the jumper from JW1 to
JW1A, etc. These jumpers have two
positions to select Alarm or
Supervisory each.

JW1A:

Alarm or supervisory

control for Relay #1.

JW2A:

Alarm or supervisory

control for Relay #2.

JW8A:

Alarm or supervisory

control for Relay #8.

Finally, there are jumpers JW1.2,
JW2.3, up to JW7.8 that allow a relay to
have the same control as an adjacent
relay. For example, starting with the
factory default setting, moving the
jumper from JW2 to JW1.2 will make
both relays 1 & 2 operate with Initiating
Circuit #1.Contact Potter Technical
Support for assistance if required.