beautypg.com

Potter PFC-5000 Series User Manual

Page 27

background image

23

Common Supervisory LED (PFC-5004 or PFC-5004E/PFC-5008 only)

The amber Common Supervisory LED illuminates steadily when there is a supervisory alarm in the panel resulting from any
latching or non-latching supervisory circuit. The LED turns off if all non-latching supervisory circuits are restored and there are
no active latching supervisory circuits. Latching supervisory alarms remain active until the panel is reset.

Common Trouble LED

The Common Trouble indicator fl ashes amber (at 20 fl ashes per minute) when the panel detects any trouble condition. It turns off
when all non-latching troubles are cleared.

Remote Trouble LED (PFC-5004 or PFC-5004E/PFC-5008 only)

The Remote Failure indicator illuminates amber if the panel detects trouble at a city tie or DACT module, or communication or
local trouble with a remote annunciator. It turns off once these conditions return to normal.

Fire Drill LED

The amber Fire Drill LED illuminates steadily while fi re drill is active.

Auxiliary Disconnect LED

The Auxiliary Disconnect Indicator fl ashes amber (20 fl ashes per minute) when the Auxiliary Disconnect switch is activated. It
turns off when the switch is activated a second time. When on, the Auxiliary Disconnect LED indicates that common alarm and
common supervisory relays, and any ARM-4 / ARM-8 relays are not activated. The trouble relay is activated. If installed, DACT
or polarity reversal and city tie modules are also inactive, causing a trouble condition.

Signal Silence LED

The amber Signal Silence LED fl ashes at the trouble fl ash rate when indication circuits are silenced either by the Signal Silence
button or by the Auto Signal Silence timer. It turns off when the signals are re-sounded by a subsequent alarm.

Battery Trouble LED

The Battery Trouble LED turns on steady when the battery is either low (below 20.4 VDC) or disconnected. It fl ashes amber at
the trouble fl ash rate if there is a Battery Charge trouble.

Ground Fault LED

The Ground Fault LED fl ashes amber at the trouble fl ash rate when the Ground Fault Detector detects a ground fault on any fi eld
wiring. It turns off when the ground fault is cleared.

Test LED

The Test LED illuminates amber when the fi re alarm panel is in walk test mode.

Circuit Status LEDs

These LEDs indicate the status of initiating circuits. They illuminate

Alarm:

Steady red

Alarm Verifi cation or waterfl ow retard in progress:

fast fl ashing red (120 fl ashes per minute)

Pending Alarm:

(see Circuit Disconnect Switches on the following page) fast fl ashing red (120 fl ashes per minute)

Supervisory:

Steady amber

Circuit Trouble LEDs

These LEDs indicate trouble for initiating and NAC circuits. They fl ash (20 fl ashes per minute) for any fi eld wiring fault, or if the
circuit has been disconnected.