beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 7

background image

Rheos Boiler and Water Heater

Page 7

SECTION 2.

Venting and Combustion Air

2.1 Combustion Air

Rheos boilers and water heaters must have

provisions for combustion and ventilation air in

accordance with section 5.3, Air for Combustion and

Ventilation, of the National Fuel Gas Code, ANSI

Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,

Installation Codes, and applicable provisions of the

local building codes.

A Rheos unit can take combustion air from the

space in which it is installed, or the combustion air can

be ducted directly to the unit. Ventilation air must be

provided in either case.

2.1.1 Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate

with the outdoors in accordance with method 1 or 2,

which follow. Where ducts are used, they shall be of

the same cross-sectional area as the free area of the

openings to which they connect.

Method 1: Two permanent openings, one

commencing within 12" (300mm) of the top and one

commencing within 12" (300mm) of the bottom, of

the enclosure shall be provided. The openings shall

communicate directly, or by ducts, with the outdoors

or spaces that freely communicate with the outdoors.

When directly communicating with the outdoors, or

when communicating to the outdoors through vertical

ducts, each opening shall have a minimum free area

of 1 square inch per 4000 Btu/hr (550 square mm/kW)

of total input rating of all equipment in the enclosure.

When communicating to the outdoors through

horizontal ducts, each opening shall have a minimum

free area of not less than 1 square inch per 2000 Btu/hr

(1100 square mm/kW) of total input rating of all

equipment in the enclosure.

Method 2: One permanent opening, commencing

within 12" (300mm) of the top of the enclosure, shall

be permitted. The opening shall directly communicate

with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces

that directly communicate with the outdoors and shall

have a minimum free area of 1 square inch per 3000

Btu/hr (734 square mm/kW) of the total input rating of

all equipment located in the enclosure. This opening

must not be less than the sum of the areas of all vent

connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform

to the requirements in the applicable codes listed

above.

In Canada, consult local building and safety

codes or, in absence of such requirements, follow

CAN/CGA B149.

2.1.2 Intake Combustion Air

The combustion air can be taken through the

wall, or through the roof. When taken from the wall, it

must be taken from out-of-doors by means of the Laars

horizontal wall terminal, shown in Table 4. See Table 3

to select the appropriate diameter air pipe. When taken

from the roof, a field-supplied rain cap or an elbow

arrangement must be used to prevent entry of rain

water (see Figure 2).

Use single-wall galvanized pipe for the

combustion air intake (see Table 5), sized per Section

1.8. Route the intake to the heater as directly as

possible. Seal all joints with tape. Provide adequate

hangers. The unit must not support the weight of the

combustion air intake pipe. Maximum linear pipe

length allowed is 50 feet (15.2m). Up to five elbows

can be used with the 50 feet of pipe. Subtract 10

allowable linear feet for every additional elbow used.

Figure 2. Combustion Air and Vent Through Roof.

Model

Intake

Exhaust

Intake

Exhaust

Size

Size

Maximum Run

Maximum Run

1200

6" (15 cm) dia.

6" (15 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

1600

8" (20 cm) dia.

6" (15 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

2000

8" (20 cm) dia.

7" (18 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

2400

8" (20 cm) dia.

10" (25 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

Table 3. Vent / Air Pipe Sizes.

This manual is related to the following products: