beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 24

background image

LAARS Heating Systems

Page 24

5.5.1 Temperature Setpoint

The temperature setpoint is the point at which the

temperature control relay will be de-energized and the

unit’s call for heat will end. The temperature setpoint

is adjusted with the setpoint dial on the A350 control

(see Figure 13). The temperature control’s sensor is in

the inlet of the unit.

5.5.2 Differential Setting

The differential is the difference in temperature

settings when the temperature control’s relay is

energized and de-energized. For instance, if the

temperature setpoint is 180°F (82°C) and the

differential is 20°F (11°C), the temperature control

will call the unit to energize at 160°F (71°C). (The

differential is the setpoint minus the differential

setting) The call for heat will end when the unit

reaches its setpoint of 180°F (82°C). The Rheos

differential is adjustable from 1°F to 30°F (1°C to

17°C). In general, the differential setting for a water

heater system will be low, so that when a storage tank

is drawing down, the heater will react to sustain a

minimum tank temperature. Boilers generally have

higher differentials than water heaters, to minimize

short cycling (see throttling range). The differential

is set by removing the cover of the A350 control

and adjusting the potentiometer marked “DIFF” (see

Figure 13).

5.5.3 Offset

The offset determines the temperature below the

controller’s setpoint where the throttling range begins.

It offsets the throttling range.

For instance, if the setpoint is 180°F (82°C) and

the offset is 5°F (3°C), then the unit’s throttling range

will begin at 175°F (79°C). Between 175°F (79°C) and

180°F (82°C), the Rheos will be in low fire.

The offset can be adjusted between 0°F and 30°F

(0°C and 17°C) by removing the cover of the S350P

control and adjusting the Offset dial (see Figure 14).

5.5.4 Throttling Range

The throttling range allows the Rheos to match

the BTU demands of varying systems, by allowing the

user to choose the temperature range through which

the unit will modulate. This will tell the controller how

fast to respond to a change in temperature. A small

throttling range keeps the unit in high fire more, and

quickens the response of the system. A larger throttling

range allows the Rheos to spread its modulating range

over a larger temperature range.

Example, Imperial units: Using a temperature

setpoint of 180°F, with a 20°F differential, a 5°F

offset, and a throttling range of 10°F, the unit will

come on at 160°F and shut off at 180°F. The offset

will set the top of the throttling range 5°F under the

setpoint, which is 175°F in this example. Therefore,

the throttling range will cause the Rheos to modulate

between 50% and 100% of full fire between 175°F and

165°F. Between 175°F and 180°F, the unit will remain

at low fire. Between 160°F and 165°F, the unit will be

at full fire.

Example, Metric units: Using a temperature

setpoint of 82°C, with a 11°C differential, a 3°C offset,

and a throttling range of 5°C, the unit will come on at

71°C and shut off at 82°C. The offset will set the top

of the throttling range 3°C under the setpoint, which is

79°C in this example. Therefore, the throttling range

will cause the Rheos to modulate between 50% and

100% of full fire between 79°C and 74°C. Between

79°C and 82°C, the unit will remain at l02 fire.

Between 71°C and 74°C, the unit will be a t full fire.

The throttling range is adjustable between 2°F

and 30°F (1°C to 17°C). The range can be set by

removing the cover of the S350P control and adjusting

the “THROT RANGE” dial (see Figure 14).

5.5.5 Minimum Output Setting

The minimum output setting of the controller is

0% of full fire. However, the minimum output of the

Rheos is limited to 50% of full fire by the fan speed

controller, to ensure proper operation of the Rheos.

If a minimum desired output is higher than 50%, the

setting can be adjusted up by removing the cover of

the S350P control and adjusting the Min Output dial

(see Figure 14). Turning the dial clockwise increases

the minimum output. In most cases, this setting should

be left as shipped from the factory, with the arrow

pointing to the 5 o'clock position.

5.5.6 Integration Constant

The proportional control used on the Rheos has

internal circuitry that helps to minimize overshoot that

can sometimes be associated with proportional plus

integral (PI) controls. There are three field-selectable

integration constants (slow, medium and fast), and

an off position on the proportional control, which

are selected with the dipswitches on the control (see

Figure 14). In most cases, this setting will not need to

be changed

Off: Switch 1 to ON position and all others to

OFF. Setting the control to the “Off” position puts the

control into proportional only operation. This is not a

recommended setting for the Rheos.

Slow: Switch 2 to ON position and all others

to OFF. This is the slowest integration constant. It

allows the Rheos the most time to reach its setpoint.

In most cases, this is too slow for Rheos installations.

Medium: Switch 3 to ON position and all others

to OFF. The integration constant is set to “Medium”

at the factory, and in most cases, will not need to be

changed. This setting will be the best suited to most

Rheos installations.

Fast: Switch 4 to ON position and all others

to OFF. If the rate of system recovery to setpoint is

This manual is related to the following products: