beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 22

background image

LAARS Heating Systems

Page 22

Figure 15. Control Parameter Graph.

through the heater is 25°F, the outlet temperature will

be 175°F (150°F+25°F). Therefore, set the manual

reset high limit to 195°F (175°F + 20°F).

Example, Metric units: If the tank temperature

is set to 60°C, set the heater’s temperature control to

66°C (60°C+6°C). Further, if the temperature rise

through the heater is 15°C, the outlet temperature will

be 81°C (66°C+15°C). Therefore, set the manual reset

high limit to 92°C (81°C+11°C).

5.4.2 Internal Water Heater

Temperature Control

When an external control is not used, the

circulator between the heater and the storage tank

must run continuously, so that the heater’s temperature

control can detect and control the water temperature in

the storage tank. The Rheos water heater’s temperature

control is adjusted to its lowest temperature position

when shipped from the factory. This is the preferred

starting point for setting the temperature control. Set

the manual reset high limit 20°F (11°C) plus heater

temperature rise above the temperature control’s

setting.

Example, Imperial units: If the heater’s

temperature control is set to 130°F, and the

temperature rise through the heater is 25°F, the outlet

temperature will be 155°F. Set the manual reset high

limit to 175°F.

Example, Metric units: If the heater’s

temperature control is set to 55°C, and the

temperature rise through the heater is 14°C, the outlet

temperature will be 69°C. Set the manual reset high

limit to 80°C.

Caution

Should overheating occur or the gas supply fail to

shut off, turn off the manual gas control valve to the

appliance.

5.5 Temperature Control Features

The Rheos temperature control is versatile and

will allow the user to better match the modulating

control to the application. Settings that can be changed

are temperature setpoint, differential, offset, throttling

range, and minimum output.

The temperature setpoint is the setting at which

the unit will shut off, having satisfied the controller’s

call for heat.

The differential determines how far the

temperature in the Rheos can fall before energizing

again.

The offset determines where the throttling range

begins.

The throttling range is the temperature range

through which the unit will modulate from minimum

to maximum firing rate.

Important Note: These control parameters work

together. Therefore, setting one parameter may have

an affect on another. Figures 15, 16 and 17 show the

relationships between these settings. Figure 15 follows

the examples that are shown in the following sections,

and Figures 16 and 17 are examples of how the

parameters can interfere with each other.

This manual is related to the following products: