beautypg.com

4 common vent test — boilers, 1 gas supply and piping – LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 15

background image

Rheos Boiler and Water Heater

Page 15

2.3.4 Vertical Combustion Air Terminal

When combustion air is taken from the roof, a

field-supplied rain cap or an elbow arrangement must

be used to prevent entry of rain water (see Figure 2).

The opening on the end of the terminal must be at least

12" (30cm) above the point at which it penetrates the

roof, and high enough above the roof line to prevent

blockage from snow. When the vent terminates on the

roof, the combustion air must terminate at least 12"

(30cm) below the vent terminal.

2.4 Common Vent Test — Boilers

NOTE: This section does not describe a method for common

venting Rheos units. It describes what must be done when a unit is

removed from a common vent system. Rheos units require special

vent systems and fan for common vent. Contact the factory if you

have questions about common venting Rheos units.

When an existing boiler is removed from a

common venting system, the common venting system

is likely to be too large for proper venting of the

appliances remaining connected to it.

At the time of removal of an existing boiler, the

following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances

remaining connected to the common venting system

are not in operation.

1. Seal any unused openings in the common venting

system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is

no blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe

condition.

3. Insofar as it is practical, close all building doors

and windows and all doors between the space in

which the appliances remaining connected to the

common venting system are located and other

spaces of the building. Turn on clothes dryers

and any appliance not connected to the common

venting system. Turn on any exhaust fans, such

as range hoods and bathroom exhausts, so they

will operate at maximum speed. Do not operate a

summer exhaust fan. Close fireplace dampers.

4. Place in operation the appliance being

inspected. Follow the lighting instructions.

Adjust thermostat so appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening

after 5 minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting

system properly vents when tested as outlined

above, return doors, windows, exhaust fans,

fireplace dampers and any other gas burning

appliance to their previous conditions of use.

7. Any improper operation of the common venting

system should be corrected so that the installation

conforms to the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and/or CSA B149.1, Installation

Codes. When resizing any portion of the common

venting system, the common venting system

should be resized to approach the minimum size

as determined using the appropriate tables in Part

II of the National Fuel Gas Code, ANSI Z223.1

NFPA 54 and/or CSA B149.1, Installation Codes.

SECTION 3.

Gas Supply and Piping

3.1 Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not the appliance.

Review the following instructions before

proceeding with the installation.

1. Verify that the appliance is fitted for the proper

type of gas by checking the rating plate. Laars

Heating Systems appliances are normally equipped

to operate at elevations up to 2000 feet (610m).

However, the appliance will function properly

without the use of high altitude modification at

elevations up to 10,000 feet (3050 m).

2. The maximum inlet gas pressure must not exceed

13" W.C. (3.2kPa). The minimum inlet natural

gas pressure is 4" W.C. (1.0kPa) and minimum

inlet propane gas pressure is 6" (1.5kPa).

3. Refer to Table 7, size supply.

Hard Water

Normal Water

Soft Water

Model Flow H/L Temp

Flow H/L Temp

Flow H/L Temp

Flow H/L Temp

Flow H/L Temp

Flow H/L Temp

(Size)

gpm feet Rise (°F) lpm

m Rise (°C) gpm feet Rise (°F) lpm

m Rise (°C) gpm feet Rise (°F) lpm

m Rise (°C)

1200

119

20

18

449 6.1

10

93

12

23

351 3.7

13

65

6.0

32

246 1.8

18

1600

161

29

17

609 8.8

10

132

20

21

500 6.1

12

89

8.9

31

336 2.7

17

2000

182

22

19

690 6.7

11

149

15

23

565 4.6

13

100 6.6

35

379 2.0

19

2400

237

23

18

898 7.0

10

186

14

23

703 4.3

13

129 6.9

32

488 2.1

18

Note:

Soft Water: 1 to 7.5 grains per gallon

Note: Headloss is for heater’s heat exchanger only.

Normal Water: 7.6 to 17 grains per gallon

Hard Water: More than 17 grains per gallon

Table 9. Water Flow Requirements, RHCV (Water Heater).

This manual is related to the following products: