Figure 36. Gas Trains.

Safety

Gas Valve

Modulating Gas

Valve Actuator

Modulating Gas

Valve Body

Manual

Gas Valve

Manual

Gas Valve

Gas Orifice

Low Gas

Pressure

Switch

High Gas

Pressure Switch

Standard and Control Pack C Gas Train

Pressure

Switch

Air Inlet

Transition

Safety

Gas Valve

Modulating Gas

Valve Actuator

Modulating Gas

Valve Body

Manual

Gas Valve

Manual

Gas Valve

Normally Open

Vent Valve

Gas Orifice

Low Gas

Pressure Switch

High Gas

Pressure Switch

Control Packs A and D Gas Train

Pressure

Switch

Air Inlet

Transition

7.2.13 Normally Open Vent Valve

Some Rheos models provide a normally open

vent valve for installations with IRI code requirements.

The valve opens when power is removed from the

safety valves. And the valve closes when the safety

valves are powered. See sections 3.1 Item #4 for

installation instructions.

7.2.14 Motorized Safety Valve

Control packs B and E have an additional

motorized safety valve. This valve is powered open

at the same time as the safety valve. To remove the

valve actuator, shut off the 120V power and the gas

shutoff valve. Remove the right side, or front panel.

Disconnect the 120V wires from the actuator. Remove

the valve actuator by taking out the four screws, and

pulling the actuator out. Re-install in reverse order.

Turn on gas shutoff valve and 120V power and

check appliance operation and tightness of gas valve

connections.

The gas valve body will rarely have to be

removed. If there is a valve problem, and it has been