beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 25

background image

Rheos Boiler and Water Heater

Page 25

sluggish with the control set to medium, the “Fast”

setting may be an improvement. The “Fast” setting

will only be used when the rate of change at the sensor

is very rapid. In most cases, this setting is too fast for

the Rheos.

5.6 External Control Connections

Rheos units are built with a selector switch and

a terminal strip to allow the Rheos to receive a 0-

10VDC signal from an external controller (such as a

building automation system or multiple boiler control).

When the selector switch is in the “Rheos

Control” position, the Rheos will be modulated by the

unit’s factory-mounted modulating control.

When the switch is in the “External Control”

position, the unit look for a 0-10VDC signal from an

external (field-supplied) controller.

To interlock the external boiler control with the

Rheos, the call for heat signal MUST be connected to

the field interlock terminal strip on the Rheos (shown

in Figure 18). Be sure to remove the factory-installed

jumper between the field interlock terminals. The

0-10VDC modulating signal MUST be connected to

external control terminal strip, located to the right

of, and behind the front panel. The terminal strip is

labeled “0-10VDC +” and 0-10VDC –” to indicate

which terminal received the hot signal (+) and which

terminal receives the common signal (-) from the

controller.

The Rheos unit will modulate between 4.7V and

10V (for 50% and 100%, respectively). Anything less

than 4.7 volts will result in 50% of full fire.

For the external control to modulate the Rheos,

the selector switch on the front panel must be in the

“External Control” position.

Important Note: DO NOT MAKE/BREAK RHEOS

LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A“call

for heat / end call for heat” MUST be connected to the

field interlock terminals. The Rheos does not recognize

0 volts as a signal to shut off. If the call for heat is not

connected between the field interlock terminals, the

Rheos will remain in low fire when it sees 0 volts as a

modulating signal.

Caution

Rheos supply voltage must not be disengaged,

except for service or isolation, or unless otherwise

instructed by procedures outlined in this manual. To

signal a call for heat, use the 24V field-interlock, as

shown in the wiring diagram(s).

Some Rheos components are designed to have

constant voltage during normal operation. If Rheos

supply voltage is toggled as a call for heat signal,

premature failure of these components may result.

5.7 Wiring Diagrams

Caution

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing

This manual is related to the following products: