beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 45

background image

Rheos Boiler and Water Heater

Page 45

SECTION 8.

Trouble Shooting

8.1 Sequence of Operation

The Rheos appliance is a cold start appliance

that should start only on a call for heat from a tank

aquastat, room thermostat, zone valve end switch or

other space temperature control device.

1. Upon a call for heat,

(a) The internal pump will start. (Pump is

optionally mounted on unit.)

(b) The blower will begin a 15 second pre-

purge.

2. Following the prepurge cycle the hot surface

ignitor will heat and will begin a 7 second trial

for ignition. The unit is allowed three attempts

for ignition.

3. The gas valve will then be energized and low-

fire (50% of full fire) ignition will occur. The

unit will remain in a low-fire start-up period for 15

seconds.

4. After the low-fire start time is over, the unit

will be in normal operation firing rate and will

modulate based on the heating load via the

temperature controller settings and readings.

5. When the call for heat is complete, or the unit

reaches its setpoint temperature, the gas valve

will close, and the fan will continue to run for

its 30 second post-purge. If a pump time delay

is used, the pump will continue to run for the

specified amount of time (adjustable from 0.1 to

10 minutes).

8.2 Resolving Lockouts

There are many causes of lockouts. The three

most common causes are: (1) inadequate gas supply,

(2) poor combustion, (3) ignitor failure (4) combustion

air.

1. Inadequate gas supply: Before proceeding, ensure

that the gas supply has not been shutoff or the LP

tank (LP boilers) is not empty. Then, restart the

boiler and observe the operational cycle. After

the pre-purge time, the unit should light. If it

does not, consult the factory.

2. Poor Combustion: Poor combustion should be

suspected if there is a strong flue gas odor. The

odor may result from an improper gas/air ratio

(high or low O

2

or CO

2

). If an improper gas/air

ratio is suspected, consult the factory.

3. Ignitor failure: If the boiler goes through a

normal start cycle but combustion does not

occur, ignitor failure should be suspected. Check

the ignitor by unplugging the ignitor plug and

measuring the ignitor resistance. It should be

50-80 (-) ohms. If the resistance is not 50-80

ohms (W), replace the ignitor. If the resistance is

correct, reset the boiler and check for 120 VAC

at the ignitor plug during the start cycle. If there

is no voltage, replace the faulty ignitor wire

harness.

4. Inadequate combustion air: If the boiler goes

through a normal ignition cycle, and shuts off

after the blower ramps up to full speed, an

abnormal restriction in the air intake or exhaust

system should be suspected. Check the air filter

for buildup of debris and clean filter if necessary.

Inspect all exhaust venting and intake venting for

blockages. Remove any blockages and inspect

and replace any damaged vent sections. If the

unit still continues to lockout after igniting,

consult the factory.
Once the reason for the lockout has been

identified and resolved you can reset the unit by

pressing the manual reset button (see Detail A in

Figure 30. Control Panel).

8.3 Delayed Ignition - Possible Causes

8.3.1 High Lockup Pressure (LP

Appliances) - Occurs on Start-up

High lock up pressure is the most common

cause of delayed ignitions on LP fueled appliances. It

may result from an improper second stage regulator

selection or from a faulty regulator.

Lock up can be detected by measuring the gas

supply pressure to the appliance at the inlet pressure

port on the gas valve. The gas supply to the appliance

must be shut off before making any connections. To

check: use a water manometer or pressure gauge with

a scale reading of at least 25 in. W.C. or 15 oz/in

2

.

(6.2kPa). Attach the manometer to the gas valve inlet

pressure port. Turn on the gas supply. The Rheos

appliance is designed to operate with supply pressures

of 4-13 in. W.C. (2.3 - 7.5 oz/ in²) (0.1-3.2kPa). If

the supply pressure exceeds 13 in. W.C. (7.5 oz/ in²)

(3.2kPa) (with the appliance off) it is possible that this

may be the cause of the delayed ignitions and the inlet

pressure must be reset to between 4-13 in. W.C. (2.3

– 7.5 oz/in

2

) (0.1-3.2kPa). Restart the appliance and

then switch it off. If the inlet gas pressure exceeds 13

in. W.C. (7.5 oz/ in²) (3.2kPa) after the appliance is

switched off, correct the lock up problem.

8.3.2 Gas Valve Regulation

Gas valve regulation problems can also cause

delayed ignitions. If gas valve regulation problems

are suspected, consult the factory. Do not attempt field

adjustment or repair.

This manual is related to the following products: