determined the actuator is working properly, the gas

valve body may need to be replaced. To remove the

gas valve body, shut off 120V power and the gas

shutoff valve. Remove the right side and front panels.

Remove the valve actuator. Unscrew the valve body

from the gas train. After the valve has been removed,

replace with a new valve in reverse order. Turn on gas

shutoff valve and 120V power and check appliance

operation and tightness of gas valve connections.

7.2.15 Gas Pressure Switches

The high and low gas pressure switches are 24V

manual reset switches that act to cut power to the gas

valves if the gas pressure is too low or too high for

proper operation. The gas pressure switches used are

integrally vent limited, and do not require venting to

atmosphere. To remove a switch, remove the screw

on the plastic housing and pull the clear cover off.

Disconnect the two wires from the screw terminals.

Twist the switch off the pipe nipple. Reassemble in

reverse order. For natural gas, set the low gas pressure

switch to 3" w.c. For propane, set the low gas pressure

switch to 5" w.c. For natural and propane, set the high

gas pressure switch to 14".

Figure 38. Control Panel.

Figure 37. Gas Train.

Solenoid Safety

Gas Valve

Modulating Gas

Valve Actuator

Modulating Gas

Valve Bodies

Manual

Gas Valve

On/Off Gas

Valve Actuator

Gas Orifice

Low Gas

Pressure Switch

Pressure

Differential

Tube Assembly

Pressure

Switch

Air Inlet

Transition

High Gas

Pressure Switch

Control Packs B and E Gas Trains

High Gas

Pressure Switch

Modulating Gas

Valve Body

Manual

Gas Valve

Solenoid Safety

Gas Valve

Air Inlet

Transition

Pressure

Switch

Gas

Orifice

Pressure

Differential

Tube Assembly

Modulating Gas

Valve Actuator

On/Off Gas

Valve Actuator

Low Gas

Pressure Switch