beautypg.com

LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 10

background image

LAARS Heating Systems

Page 10

Model and

Distance from Gas Meter or Last Stage Regulator

Gas Type

0-50 feet

0-15m

50-100 feet 15-31m

100-200 feet 31-61m

200-300 feet

61-91m

1200 natural

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

1200 propane

1-1/2"

3.8cm

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

1600 natural

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1600 propane

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

2000 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2000 propane

2-1/2"

6.4cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

2400 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2400 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

Notes:

1. These figures are based on 1/2" 0.12kPa water column pressure drop.

2. Check supply pressure and local code requirements before proceeding with work.

3. Pipe fittings must be considered when determining gas pipe sizing.

Table 7. Gas Piping Sizes.

3. Locate the vent terminal so that vent gases cannot

be drawn into air conditioning system inlets.

4. Locate the vent terminal so that vent gases cannot

enter the building through doors, windows,

gravity inlets or other openings. Whenever

possible, locations under windows or near doors

should be avoided.

5. Locate the vent terminal so that it cannot be

blocked by snow. The installer may determine

that a vent terminal must be higher than the

minimum shown in codes, depending upon local

conditions.

6. Locate the terminal so the vent exhaust does

not settle on building surfaces or other nearby

objects. Vent products may damage such

surfaces or objects.

7. If the boiler or water heater uses ducted

combustion air from an intake terminal located

on the same wall, locate the vent terminal at least

3 feet (0.9m) horizontally from the combustion

air terminal, and locate the vent terminal at least

1 foot (0.3m) above the combustion air terminal.

From Massachusetts Rules and Regulations

248 CMR 5.08:

(a) For all side wall horizontally vented gas

fueled equipment installed in every dwelling,

building or structure used in whole or inpart

for residential purposes, including those

owned or operated by the Commonwealth and

where the side wall exhaust vent termination

is less than seven (7) feet above finished grade

in the area of the venting, including but not

limited to decks and porches, the following

requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE

DETECTORS.

At the time of installation of the side wall

horizontal vented gas fueled equipment, the

installing plumber or gasfitter shall observe that

a hard-wired carbon monoxide detector with

an alarm and battery back-up is installed on

the floor level where the gas equipment is to be

installed. In addition, the installing plumber or

gasfitter shall observe that a battery operated or

hard-wired carbon monoxide detector with an

alarm is installed on each additional level of the

dwelling, building or structure served by the side

wall horizontal vented gas fueled equipment.

It shall be the responsibility of the property

owner to secure the services of qualified licensed

professionals for the installation of hard-wired

carbon monoxide detectors.

a.

In the event that the side wall

horizontally vented gas fueled equipment is

installed in a crawl space or an attic, thehard-

wired carbon monoxide detector with alarm

and battery back-up may be installed on the

next adjacent floor level.

b.

In the event that the requirements of

this subdivision cannot be met at the time of

completion of installation, the owner shall

have a period of thirty (30) days to comply

with the above requirements; provided,

however, that during said thirty (30) day

period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE

DETECTORS.

Each carbon monoxide detector as required

in accordance with the above provisions shall

comply with NFPA 720 and be ANSI/UL 2034

listed and IAS certified.

3. SIGNAGE.

A metal or plastic identification plate shall be

permanently mounted to the exterior of the

building at a minimum height of eight (8) feet

This manual is related to the following products: