Voice event notification, X10 operation – Interlogix Simon XT Installation Manual User Manual
Page 68

62
Simon XT Installation Manual
Table 32: Audio verification set
Phone button
Function
0 or 1
Speak
2
VOX operation
3 or 6
Listen
7
Extend session for 90 more seconds
88
Terminates session with call back (the panel answers
on the first ring if called within 5 minutes)
99
Terminates session with no call back
Voice event notification
Testing this feature requires two people; one at the alarm site and the other at
the location the panel is programmed to call.
To test voice event notification:
1. Contact the central monitoring station (if the system is monitored) to inform
them you are testing the system and not to dispatch authorities.
2. At the system site, put the system into an alarm condition.
3. At the calling location, pick up the phone after it starts ringing. You should
hear the panel voice announce Press Star for Alarm.
4. Press * and the panel voice identifies the alarm. If there is more than one
alarm in progress, you must press * for the panel voice to identify them.
After all alarms have been identified, the panel announces Press # to Exit.
5. Press # to terminate the call.
You must terminate the call by pressing #. Otherwise, the panel may not
disconnect from the phone line for up to 2 minutes.
X10 operation
The following sections describe how to test X10 lamp, siren, appliance, and
universal module operation.
Manual lamp module control
• Control panel: Press the asterisk button (*) and the unit number of the lamp
module using the numeric buttons to test individual lamp modules 1 through
8. The panel responds with Light # on/off. Press the asterisk button (*) twice
to turn on all lamp modules. Press the pound button (#) twice to turn off all
lamp modules.