Wall Mount Installation (Optional)

Duct Sensor Installation

When the control panel is ordered, the system typically consists of one duct sensor per hood exhaust
riser. These sensors are typically shipped factory installed in factory assembled hood risers. If the risers
are field cut, the sensor and other components are shipped loose for field installation as shown below. A
hole must be cut in the grease duct, and the quick seal and sensor must be assembled as shown below.
A 2-wire plenum rated thermistor cable (18 gauge typical), run in conduit, should be used to wire the
sensors back to the controller and landed on connector J10 as indicated on the installation schematic.

Mount control panel with adequate
clearance from excessive heat
sources such as appliances to prevent
damage of the components.

IMPORTANT!!

When exhaust duct connections are located and cut in the field, duct temperature probes are
shipped loose in the electrical package enclosure. These must be installed in the duct
immediately above the hood for proper system operation.