13. Adjust Wash Time (Min): (Factory Default: 3 min):

This option is available if the control system includes self-cleaning option from the factory. The
wash time value is setup in minutes with a maximum value of 30 minutes.
Starting from the Main menu, press the MENU button. Screen displays “Configuration” Press the
ENTER button. Press DOWN or UP until the screen displays “Misc Options”. Press ENTER.
Press UP or DOWN until the screen displays “Set Wash Time”. Press ENTER. Press UP or
DOWN to adjust the time value. Press ENTER
Press MENU multiple times to get out to the main menu and reboot the processor.

14. Set Wash Min Fan Runtime (Factory Default: 480 min):

This option is available if the control system includes self-cleaning option from the factory. Its
maximum value is 1440 minutes or 24 hours. Refer to the Self-Cleaning Section under
Functionality for more details about this option.
Starting from the Main menu of HMI

, press DOWN or UP until the screen displays “Misc Options”.

Press ENTER. Press UP or DOWN until the screen displays “Set Wash Min Fan Runtime”. Press
ENTER. Press UP or DOWN to adjust the time value. Press ENTER. Press MENU multiple times
to get back to the main menu or one more time to reboot the processor.

15. Set Wash Min Interval Time (Factory Default: 720 min):

This option is available if the control system includes self-cleaning option from the factory. Its
maximum value is 1440 minutes or 24 hours. Refer to the Self-Cleaning Section under
Functionality for more details about this option.
Starting from the Main menu of HMI

, press DOWN or UP until the screen displays “Misc Options”.

Press ENTER. Press UP or DOWN until the screen displays “Set Wash Min Interval time”. Press
ENTER. Press UP or DOWN to adjust the time value. Press ENTER. Press MENU multiple times
to get back to the main menu or one more time to reboot the processor.

16. Adjust the number of PCU Advanced Filter Monitoring (AFM) Units

If PCU AFM units are connected to the control panel (through Modbus), the number of units has
to be adjusted through this parameter. Refer to the PCU AFM manual for additional information
on how to setup the PCU AFM unit number at the unit control panel.
Starting from the Main menu, press the MENU button. Screen displays “Configuration” Press the
ENTER button. Press DOWN or UP until the screen displays “Misc Options”. Press ENTER.
Press UP or DOWN until the screen displays “Set Number of PCU AFM”. Press ENTER. Press
UP or DOWN to adjust the number of units. Press ENTER. Press MENU multiple times to get out
to the main menu and reboot the processor.

17. Set HMI Dimming (Factory Default: OFF)

Starting from the Main menu,

press the MENU button. Screen displays “Configuration” Press the

ENTER button. Press DOWN or UP until the screen

displays “Misc Options”. Press ENTER.

Press UP or DOWN until the screen displays “Set HMI Dimming”. Press ENTER. Press UP or
DOWN to turn this option ON or OFF. Press ENTER. Press MENU multiple times to get back to
the main menu or one more time to reboot the processor.

18. Set Dim Delay Time(Factory Default: 60sec)

This option is only accessible when HMI dimming is ENABLED. It allows the user to modify the
time for which the backlight of the HMI remains on before it will turn off. The Dim Delay Time is
factory set to 60 seconds, and is refreshable every time a button on the HMI is pressed. The Dim
Delay Time is adjustable between 10 seconds and 5 minutes.
Starting from the Main menu,

press the MENU button. Screen displays “Configuration”. Press the

ENTER button. P

ress DOWN or UP until the screen displays “Misc Options”. Press ENTER.

Press UP or DOWN until the screen displays “Set DimDelay Time”. Press ENTER. Press UP or
DOWN to adjust the time value. Press ENTER
Press MENU multiple times to get back to the main menu or one more time to reboot the
processor.