Operation, Start-up procedure – FloAire Electrical Controls User Manual
Page 10
![background image](/manuals/676125/10/background.png)
A0023032
August 2014 Rev. 7
10
OPERATION
Start-Up Procedure
NOTE: FIRE system must be in ARMED state before proceeding.
1. Once all required connections have been completed as indicated on the installation schematic,
startup can begin. Apply power to the panel. The ECPM03 board and the HMI will power up and
beep. If that is not the case, check all power connections. Verify that there is no alarm message
displayed on any HMI screen. If there are alarms present, you can press the MUTE button to
silence the alarm and then work to resolve them.
A HMI has 4 buttons; function is displayed adjacent to them on the screen. These functions will
change depending on the status of the panel. If no text is adjacent to the button, it does not have
a function.
Typically LIGHTS and FANS functions are shown on the bottom 2 buttons. The status of those
elements is shown by the shading used inside the box associated with the function. An empty box
around the FAN function means that the FANS are turned OFF. A dark box around the FAN
function means that the FANS are turned ON. The same applies to LIGHTS.
Note: For the rest of the document, the term button will be used to refer to either the actual button
or the function associated with it.
The center two lines of the HMI are reserved for displaying informational or fault messages
When a fault occurs, an audible alarm is triggered and a message is displayed on the HMI(s).
The Audible Alarm can be silenced by pushing the Mute button that appears on the top right
corner.
2. Press the Lights button on the HMI to energize the hood lights. If the lights do not come on,
make sure the light bulbs are installed and/or check the lighting circuit.
3. Press the Fans button on the HMI to energize the fans.
If there are multiple fan zones, pressing the Fans button on the first HMI will only energize the
fans in zone #1. Pressing the Fans button on the second HMI will energize the fans in zone #2.
If the supply fan does not come ON, verify that there is not a Fire Condition Alarm on the screen.
If that is the case, the fire system might be tripped or not properly wired.
4. If cooking appliances are connected to an Electric gas valve controlled by the control panel, the
gas valve can be turned ON by pressing the Gas Reset button on the top right corner of the HMI.
The icon will only show if the Gas Valve Option is turned ON under the ECPM03 menu:
Configuration / Misc. Options / Set Gas Valve, or if a CORE fire protection system is enabled.
Button
Associated
function