FloAire Electrical Controls User Manual
Page 11
![background image](/manuals/676125/11/background.png)
A0023032
August 2014 Rev. 7
11
5. Turn the Fans off. Turn on the cooking appliance(s) and allow them to reach idle temperature.
The fans should automatically activate as the cooking appliance(s) heats up. The factory set
activation point for duct temperature override of the fan switch is 15 degrees above kitchen room
temperature. Each duct temperature sensor has its own temperature offset setting. These values
should be adjusted based on the cooking appliances and cooking load. Refer to paragraph (e)
under the Configuration section for further details.
6. If the controls include the Self Cleaning or Hood CORE Protection Fire System option, a Wash
button will be displayed on the HMI screen. Push the button to start the wash cycle. Water will be
sprayed in the plenum and duct of the hood and surfactant will be injected at a predetermined
frequency. The wash cycle will stop when the wash timer expires or when the Stop Wash button
is pressed.
Make sure Hood filters remain in place during the wash cycle.
7. If the controls include the Proving Interlock Option, as indicated on the installation schematic with
current sensors included inside the package, a calibration step is required at startup. Please refer
to the Fan Proving Interlock section below under Functionality for further details about this
function. To perform the calibration, refer to paragraph (i) under the Configuration section.