EVCO EK354AJ7 User Manual

Page 4

background image

The indications showed by the instrument flashes, except the indications “E1“ , “AL1“

and “AL2“ (they are alternated with the temperature the chamber probe is reading)

and the buzzer utters an intermittent beep.

10

TECHNICAL DATA

10.1 Technical data

Box: self-extinguishing grey.

Size: 72 x 144 x 79 mm (2.83 x 5.66 x 3.11 in).

Installation: panel mounting, panel cut out 67 x 138 mm (2.63 x 5.43 in), with screw

brackets (supplied by the builder).

Frontal protection: IP 54.

Connections: extractable terminal blocks with pitch 7.5 mm (0.29 in) for cables up

11

WORKING SETPOINT AND CONFIGURATION PARAMETERS

11.1 Working setpoint

LABEL MIN. MAX. U.M.

DEF. WORKING SETPOINT

rA1

rA2

°C/°F

(8)

0

working setpoint

11.2 First level parameters

LABEL MIN. MAX. U.M.

DEF. PASSWORD

PA

-90

100

---

0

password

LABEL MIN. MAX. U.M.

DEF. MEASURE INPUTS

/1

-10

10

°C/°F

(8)

0

chamber probe calibration

LABEL MIN. MAX. U.M.

DEF. REGULATOR

rA0

-15

-1

°C/°F

(8)

-2

hysteresis (differential, it is relative to the working setpoint)

LABEL MIN. MAX. U.M.

DEF. STEAM (by request)

rb0

-15

-1

°C/°F

(8)

-2

hysteresis (differential, it is relative to rb1)

11.3 Second level parameters

LABEL MIN. MAX. U.M.

DEF. MEASURE INPUTS

/0

10

11

---

10

kind of probe (10 = “J” Tc, 11 = “K” Tc)

/1

-10

10

°C/°F

(8)

0

chamber probe calibration

/2

0

6

---

3

probe reading speed (0 = fast, ... , 6 = slow)

/4

0

1

---

0

display of non meaningful zeros (1 = YES)

/8

0

1

---

1

unit of measure temperature (0 = Fahrenheit degree, 1 = Celsius degree)

LABEL MIN. MAX. U.M.

DEF. REGULATOR

rA0

-15

-1

°C/°F

(8)

-2

hysteresis (differential, it is relative to the working setpoint)

rA1

0

rA2

°C/°F

(8)

0

minimum value you can assign to the working setpoint

rA2

rA1

999

°C/°F

(8)

300

maximum value you can assign to the working setpoint

LABEL MIN. MAX. U.M.

DEF. STEAM (by request)

rb0

-15

-1

°C/°F

(8)

-2

hysteresis (differential, it is relative to rb1)

rb1

0

999

°C/°F

(8)

0

steam setpoint

rbA

---

---

°C/°F

(8)

---

steam temperature showing

rbE

-99

-1

°C/°F

(8)

-50

temperature below which the steam injection will not be allowed (it is relative to rb1)

(9)

cold joint

alarm

first

tempera-

ture

alarm

second

tempera-

ture

alarm

• the temperature the

steam probe is read-

ing is outside the lim-

its allowed by the

working range of

the instrument

there is a defect in the

cold joint of the instru-

ment

the temperature the

chamber probe is

reading is outside the

limit you have set with

parameter AA1

the temperature the

chamber probe is

reading is outside the

limit you have set with

parameter Ab1

turn OFF the power

supply of the instru-

ment: unless the alarm

disappears, you will

have to change the

instrument

test the temperature

close to the probe (look

at parameters AA0,

AA1 and AA4)

test the temperature

close to the probe (look

at parameters Ab0,

Ab1 and Ab4)

• the top output will

be turned OFF

• the floor output will

be turned OFF

• if the instrument

has been preset for

steam temperature

regulation, the

steam generator will

be turned OFF and

the steam injection

will not be allowed

no effect

no effect

to 2.5 mm² (0.38 sq in, power supply and outputs) and with pitch 5 mm (0.19 in) for

cables up to 2.5 mm² (0.38 sq in, input).

Ambient temperature: from 0 to 55 °C (32 to 131 °F, 10 ... 90% of relative humidity

without condensate).

Power supply: 230 Vac, 50/60 Hz, 4 VA (standard) or 115 Vac, 50/60 Hz, 4 VA

(by request).

Alarm buzzer: included.

Measure inputs: 1 (chamber probe) for “J” or “K” thermocouples; steam probe by

request (for steam temperature regulation).

Working range: from 0 to 700 °C (32 to 999 °F) for “J” thermocouple,

from 0 to 999 °C (32 to 999 °F) for “K” thermocouple.

Setpoint range: from 0 to 999 °C (0 to 999 °F).

Range of the timer for delayed starting: from 1 to 99 h.

Range of the cooking timer: from 1 to 99 min.

Resolution: 1 °F with unit of measure in Fahrenheit, 1 °C with unit of measure in

Celsius.

Display: one red LED 3-digit displays 13.2 mm (0.51 in) high, one red LED 2-digit

display 13.2 mm (0.51 in) high, two LED bars (10 red LED), output status indicators,

indicators of the unit of measure of the temperature showed by the instrument.

Outputs: 6 relays: one 8 A @ 250 Vac relay for top heating group control (NO),

one 8 A @ 250 Vac relay for floor heating group control (NO), one 10 A @ 250 Vac relay

for steam generator control (NO), one 8 A @ 250 Vac relay for steam injection control

(NO), one 8 A @ 250 Vac relay for extractor control (NO), one 8 A @ 250 Vac relay for

chamber light control (NO); the maximum current allowed on terminal 21 and 26 is

10 A.