CONFIGURATION PARAMETERS (1/2)
NOTE CODE PARAMETER
DESCRIPTION
MIN.
MAX.
U.M.
STAND.
(1)
PA
password
-55
99
---
---
/
MEASURE INPUTS
(1)
/1
calibration (ref. to the cabinet probe)
-10
+10
°
C
0
c
QUICK-COOLING/FREEZING AND COLD-STORING ON-OFF REGULATOR
(1)
c0
hysteresis (differential, ref. to the cabinet probe)
+1
+15
°
C
+2
(1)
c1
maximum length of the quick-cooling for temperature
1
400
min.
90
(1)
c2
quick-cooling for temperature cut off set (ref. to the needle probe)
-55
+99
°
C
+10
(1)
c3
cold-storing set (ref. to the cabinet probe)
-55
+99
°
C
+3
(1)
c4
maximum length of the quick-freezing for temperature
1
400
min.
270
(1)
c5
quick-freezing for temperature cut off set (ref. to the needle probe)
-55
+99
°
C
-18
(1)
c6
very cold-storing set (ref. to the cabinet probe)
-55
+99
°
C
-25
c7
threshold for needle probe properly positioned fast-test
0
+99
°
C
+30
(1)
c8
quick-cooling/freezing for temperature enabling set (ref. to the needle probe)
-55
+99
°
C
+65
c9
alarm buzzer activation length when a quick-cooling/freezing ends
0
99
sec.
3
(1)(2) cA
needle probe reading
---
---
°
C
---
(1)
cb
quick-cooling working set (ref. to the cabinet probe)
-55
+99
°
C
-10
(1)
cC
quick-freezing working set (ref. to the cabinet probe)
-55
+99
°
C
-55
(1)
cd
Hard-phase cut off set (ref. to the needle probe)
-55
+99
°
C
-15
cE
during of the needle probe properly positioned differential-test
1
99
sec.
255
(1)
cF
Hard-phase working set (ref. to the cabinet probe)
-55
+99
°
C
+15
t
HARD-PHASE DURING A QUICK-COOLING FOR TIME
C0
Hard-phase during
1
400
min.
60
C
COMPRESSOR OUTPUT PROTECTIONS
C0
disabling time at the output activation from the instrument start
0
99
min.
0
C1
disabling time at the output activation from the preceding activation
0
99
min.
0
C2
disabling time at the output activation from the preceding deactivation
0
99
min.
0
C5
cycle time for the output activation in case of cabinet probe failure
0
99
min.
10
C6
output activation length during the cold-storing in case of cabinet probe failure
0
99
min.
3
C7
output activation length during the very cold-storing in case of cabinet probe failure
0
99
min.
8
d
DEFROST REGULATOR
(3)
d0
defrost interval
0
99
hours/min.
8
(4)
d1
kind of defrost
0
2
---
1
d2
defrost cut off set (ref. to the evaporator probe)
-55
+99
°
C
+2
d3
maximum defrost length
1
99
min./sec.
30
d5
first defrost intervall from the begin of the cold-storing phase
0
99
min.
0
d4
defrost at the beginning of the quick-cooling/freezing 0=NO; 1=YES
0
1
---
0
d7
dripping length
0
99
min./sec.
2
(5)
d9
forced defrost (delays override)
0
1
---
0
(1)(2) dA
evaporator probe reading
---
---
°
C
---
(6)
db
times base for the parameters d0, d3, d7 and F5
0
1
---
0
F
EVAPORATOR FANS REGULATOR
(7)
F0
output activity
0
1
---
0
F1
output deactivation set (ref. to the evaporator probe)
-55
+99
°
C
-1
F2
hysteresis (differential, ref. to the evaporator probe)
+1
+15
°
C
+1
F3
output deactivated if the compressor is deactivated
0=NO; 1=YES
0
1
---
1
F4
output deactivated during the defrost
0=NO; 1=YES
0
1
---
1
F5
disabling time at the output activation from the end of the dripping
0
99
min./sec.
3
u
DIGITAL INPUTS
(8)
u0
door-switch activate cabinet light output
0=NO; 1=YES
0
1
---
1