PROTECTION — Once the units are properly positioned on

the jobsite, they must be covered with either a shipping carton,

vinyl film, or an equivalent protective covering. Open ends of

pipes stored on the jobsite must be capped. This precaution is

especially important in areas where painting, plastering, or

spraying of fireproof material, etc. is not yet complete. Foreign

material that is allowed to accumulate within the units can pre-

vent proper start-up and necessitate costly clean-up operations.

Before installing any of the system components, be sure to

examine each pipe, fitting, and valve, and remove any dirt or

foreign material found in or on these components.

INSPECT UNIT — To prepare the unit for installation, com-

plete the procedures listed below:

1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the

correct unit has been shipped.

2. Do not remove the packaging until the unit is ready for

installation.

3. Verify that the unit’s refrigerant tubing is free of kinks or

dents, and that it does not touch other unit components.

4. Inspect all electrical connections. Be sure connections are

clean and tight at their terminations.

5. Loosen compressor bolts until the compressor rides freely

on springs. Remove shipping restraints.

6. Remove the four

1

/

4

in. (6 mm) shipping bolts from com-

pressor support plate (two bolts on each side) to maxi-

mize vibration and sound alternation.

7. Remove any blower support cardboard from inlet of the

blower.

8. Locate and verify any accessory kit located in compressor

and/or blower section.

9. Remove any access panel screws that may be difficult to

remove once unit is installed.

Step 3 — Locate Unit —

The following guidelines

should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between

4.4 C and 37.8 C and relative humidity is no greater than

75%.

• Provide sufficient space for water, electrical and duct

connections.
NOTE: Water inlets/outlets and high/low voltage electrical

access are available on either side of the unit. Electrical ac-

cess is also available on the unit front. See Fig. 2 and 3.

• Locate unit in an area that allows for easy access and

removal of filter and access panels.
NOTE: Unit has full filter frame bottom access for 25, 51,

or 102 mm filters.

• ALLOW enough space for service personnel to perform

maintenance.

• Provisions must be made for return air to freely enter the

space if unit needs to be installed in a confined area such

as a closet.

Step 4 — Mount the Unit —

Vertical units are avail-

able in rear or front return air configurations.
DISCHARGE CONFIGURATION CONVERSION — To

change the discharge configuration of the unit from top dis-

charge to straight (right or left) discharge, follow the procedure

below. To change the discharge configuration of the unit from

straight (right or left) discharge to top discharge, reverse the

procedure below.

1. Remove the 3 panels as shown in Fig. 4.

2. Remove blockoff air handler. Loosen belt and remove.

See. Fig. 5.

3. Remove 4 bolts from blower panel. Remove 4 bolts (2

bolts on each side) from blower sides. See Fig. 6.

CAUTION

DO NOT store or install units in corrosive environments or

in locations subject to temperature or humidity extremes

(e.g., attics, garages, rooftops, etc.). Corrosive conditions

and high temperature or humidity can significantly reduce

performance, reliability, and service life. Always move

units in an upright position. Tilting units on their sides may

cause equipment damage.

CAUTION

Failure to remove shipping brackets from spring-mounted

compressors will cause excessive noise and could cause

component failure due to added vibration.

Fig. 4 — Remove Panels

BLOWER ACCESS

PANEL

C-BOX/

MOTOR ACCESS

PANEL

COMPRESSOR

ACCESS PANEL

a50-8466

Fig. 5 — Remove Blockoff Air Handler and Belt

BLOCKOFF

AIR HANDLER

a50-8467

Fig. 6 — Remove Bolts from

Blower Panel and Sides

STEP 3

STEP 3

a50-8468