Table 1 — 50VQP Unit Physical Data

LEGEND

NOTES:

1. All units have grommet and spring compressor mountings, and

2.2 cm and 3.5 cm electrical knockouts.

2. Use the lowest maximum pressure rating when multiple options

are combined:

UNIT 50VQP

084

096

120

150

168

192

240

300

COMPRESSOR QUANTITY

Scroll (1)

Scroll (2)

Factory Charge HFC-410A (kg) per circuit

3.97

4.42

6.35

7.03

3.97

4.42

6.35

7.03

BLOWER MOTOR
Blower Motor Quantity

1

Standard Motor (kW)

.75

1.12

1.49

2.24

1.49

2.24

3.73

3.73

Large Motor (kW)

1.12

1.49

2.24

3.73

2.24

3.73

5.60

5.60

BLOWER
No. of Blowers

1

2

Blower Wheel Size D x W (cm)

38.1 x 27.9

38.1 x

38.1

38.1 x 27.9

38.1 x

38.1

WATER CONNECTION SIZE

FPT (in.) [mm]

1-1/2 [38.1]

2 [50.8]

2-1/2

[63.5]

COAX VOLUME
Volume (liters)

8.28

9.37

13.11

18.29

24.08

27.98

CONDENSATE CONNECTION SIZE
FPT (in.) [mm]

1 [25.4]

AIR COIL DATA
Air Coil Dimensions H x W (cm)

91.4 x 121.9

91.4 x 121.9

Air Coil Total Face Area (sq m)

1.11

2.22

Air Coil Tube Size (cm)

3/8 [0.953]

Air Coil Fin Spacing (fins per cm)

5.5

4.72

5.5

4.72

Air Coil Number of Rows

2

3

4

2

3

4

MISCELLANEOUS DATA
Filter Standard Throwaway (qty) (cm)

(4) 45.74 x 63.5 x 2.5

(8) 45.74 x 63.5 x 2.5

Weight - Operating (kg)

399

422

435

725

755

769

Weight - Packaged (kg)

406

429

442

739

769

782

FPT — Female Pipe Thread

OPTION

MAXIMUM PRESSURE (kPa)

Base Unit

3100

Motorized Water Valve

2750

Internal Secondary Pump

999

T

Optional Discharge

Supply Air

Optional Discharge

Access
Panel

Access
Panel

Access
Panel

Access
Panel

Vibration
Pad

Control Box

Supply Air

Supply Water

Return
Water

Balancing
Valve

Valves

Trap

Condensate

24 V Remote
Mtd. Stat

Power
Supply

Disconnect
Switch or
Per Local Codes

Condensate

Water In

Water Out

Unions

Fig. 1 — Typical 50VQP Unit Installation