Units with Aquazone™ Complete C Control

STANDBY — Y and W terminals are not active in Standby

mode, however the O and G terminals may be active, de-

pending on the application. The compressor will be off.
COOLING — Y and O terminals are active in Cooling

mode. After power up, the first call to the compressor will

initiate a 5 to 80 second random start delay and a 5-minute

anti-short cycle protection time delay. After both delays are

complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start

delay is omitted.
HEATING STAGE 1 — Terminal Y is active in heating

stage 1. After power up, the first call to the compressor will

initiate a 5 to 80 second random start delay and a 5-minute

anti-short cycle protection time delay. After both delays are

complete, the compressor is energized.
NOTE: On all subsequent compressor calls the random start

delay is omitted.
HEATING STAGE 2 — To enter Stage 2 mode, terminal W

is active (Y is already active). Also, the G terminal must be

active or the W terminal is disregarded. The compressor re-

lay will remain on and EH1 is immediately turned on. EH2

will turn on after 10 minutes of continual stage 2 demand.
NOTE: EH2 will not turn on (or if on, will turn off) if FP1

temperature is greater than 7.2 C and FP2 is greater than

48.9 C.
EMERGENCY HEAT — In emergency heat mode, termi-

nal W is active while terminal Y is not. Terminal G must be

active or the W terminal is disregarded. EH1 is immediately

turned on. EH2 will turn on after 5 minutes of continual

emergency heat demand.

Units with Aquazone Deluxe D Control

STANDBY/FAN ONLY — The compressor will be off.

The Fan Enable, Fan Speed, and reversing valve (RV) relays

will be on if inputs are present. If there is a Fan 1 demand,

the Fan Enable will immediately turn on. If there is a Fan 2

demand, the Fan Enable and Fan Speed will immediately

turn on.
NOTE: DIP switch 5 on S1 does not have an effect upon

Fan 1 and Fan 2 outputs.
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan

Enable and Compressor relays are turned on immediately.

Once the demand is removed, the relays are turned off and

the control reverts to Standby mode. If there is a master/

slave or dual compressor application, all compressor relays

and related functions will operate per their associated DIP

switch 2 setting on S1.
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan

Enable and Compressor relays are remain on. The Fan

Speed relay is turned on immediately and turned off imme-

diately once the demand is removed. The control reverts to

Heating Stage 1 mode. If there is a master/slave or dual

compressor application, all compressor relays and related

functions will operate per their associated DIP switch 2 set-

ting on S1.
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan

Enable, Fan Speed and Compressor relays remain on. The EH1

output is turned on immediately. With continuing Heat Stage 3

demand, EH2 will turn on after 10 minutes. EH1 and EH2 are

turned off immediately when the Heating Stage 3 demand is re-

moved. The control reverts to Heating Stage 2 mode.

Output EH2 will be off if FP1 is greater than 7.2 C and

FP2 (when shorted) is greater than 48.9 C during Heating

Stage 3 mode. This condition will have a 30-second

recognition time. Also, during Heating Stage 3 mode, EH1,

EH2, Fan Enable, and Fan Speed will be ON if G input is

not active.
EMERGENCY HEAT — In Emergency Heat mode, the

Fan Enable and Fan Speed relays are turned on. The EH1

output is turned on immediately. With continuing Emergen-

cy Heat demand, EH2 will turn on after 5 minutes. Fan En-

able and Fan Speed relays are turned off after a 60-second

delay. The control reverts to Standby mode.

Output EH1, EH2, Fan Enable, and Fan Speed will be

ON if the G input is not active during Emergency Heat

mode.
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan

Enable, compressor and RV relays are turned on immediate-

ly. If configured as stage 2 (DIP switch set to OFF) then the

compressor and fan will not turn on until there is a stage 2

demand. The Fan Enable and compressor relays are turned

off immediately when the Cooling Stage 1 demand is re-

moved. The control reverts to Standby mode. The RV relay

remains on until there is a heating demand. If there is a mas-

ter/slave or dual compressor application, all compressor re-

lays and related functions will track with their associated

DIP switch 2 on S1.
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan

Enable, compressor and RV relays remain on. The Fan

Speed relay is turned on immediately and turned off once

the Cooling Stage 2 demand is removed. The control reverts

to Cooling Stage 1 mode. If there is a master/slave or dual

compressor application, all compressor relays and related

functions will track with their associated DIP switch 2 on

S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In

NLL staged Heating mode, the override (OVR) input be-

comes active and is recognized as a call for heating and the

control will immediately go into a Heating Stage 1 mode.

With an additional 30 minutes of NLL demand, the control

will go into Heating Stage 2 mode. With another additional

30 minutes of NLL demand, the control will go into Heating

Stage 3 mode.

COMPLETE C AND DELUXE D BOARD

SYSTEM TEST

System testing provides the ability to check the control

operation. The control enters a 20-minute Test mode by mo-

mentarily shorting the test pins. All time delays are in-

creased 15 times.

Test Mode —

To enter Test mode on Complete C or De-

luxe D controls, cycle the power 3 times within 60 seconds.

The LED (light-emitting diode) will flash a code representing

the last fault when entering the Test mode. The alarm relay will

also power on and off during Test mode. See Tables 20-22. To

exit Test mode, short the terminals for 3 seconds or cycle the

power 3 times within 60 seconds.
NOTE: The Deluxe D control has a flashing code and alarm

relay cycling code that will both have the same numerical

label. For example, flashing code 1 will have an alarm relay

cycling code 1. Code 1 indicates the control has not faulted

since the last power off to power on sequence.