EVCO EVXV215N7 User Manual
Page 7
EVCO S.p.A. • Code 104X201E314 • page 7/9
i3
-1
120
min
15
15
15
15
i4
0
1
- - - -
0
0
0
0
i5
0
6
- - - -
not avail. not avail.
2
2
i6
0
1
- - - -
not avail. not avail.
0
0
i7
0
120
min
not avail. not avail.
0
0
i8
0
15
- - - -
not avail. not avail.
0
0
i9
1
999
min
not avail. not avail.
240
240
i10
0
999
min
not avail.
0
0
0
i11
0
240
s
not avail.
15
15
15
i12
0
240
s
not avail.
60
60
60
i13
0
240
- - - -
not avail.
180
180
180
i14
0
240
min
not avail.
32
32
32
PAR.
MIN.
MAX. UM
EVXV201 EVXV203EVXV204/5EVXV214/5
u1
0
6
- - - -
not avail. not avail.
0
0
u2
0
1
- - - -
not avail. not avail.
0
0
u4
0
1
- - - -
not avail. not avail.
1
1
u5
-99.0 99.0
°C/°F (1)
not avail. not avail.
-1.0
-1.0
u6
1
120
min
not avail. not avail.
5
5
u7
0.0
99.0
°C/°F (1)
not avail. not avail.
2.0
2.0
u8
0
1
- - - -
not avail. not avail.
0
0
u9
0
1
- - - -
1
1
1
1
u11
0
6
- - - -
not avail. not avail.
3
3
PAR.
MIN.
MAX. UM
EVXV201 EVXV203EVXV204/5EVXV214/5
HE1
00:00 23:59 hr:min
not avail. not avail.
00:00
00:00
HE2
00:00 23:59 hr:min
not avail. not avail.
00:00
00:00
PAR.
MIN.
MAX. UM
EVXV201 EVXV203EVXV204/5EVXV214/5
Hd1
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
Hd2
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
Hd3
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
Hd4
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
Hd5
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
Hd6
00:00 23:59 hr:min
not avail. not avail.
- - : - -
- - : - -
PAR.
MIN.
MAX. UM
EVXV201 EVXV203EVXV204/5EVXV214/5
LA
1
247
- - - -
247
247
247
247
Lb
0
3
- - - -
2
2
2
2
LP
0
2
- - - -
2
2
2
2
maximum duration of the effect caused by activation of the door microswitch on the compressor and the evaporator fan (the evaporator
fan in EVXV203, EVXV204, EVXV214, EVXV205 and EVXV215 only)
-1= the effect will last until the input is disactivated
storage of door microswitch input alarm (code “id”) (20)
1 = YES
effect caused by the activation of the multifunction input
0 = no effect
1 = SYNCHRONISATION OF DEFROSTING PERIODS - once time d5 has passed defrosting will be activated
2 = ACTIVATION OF ENERGY SAVING FUNCTION - the Energy Saving function will be activated (until the input is disactived), provided the
Overcooling function is running; see also r4
3 = ACTIVATION OF MULTIFUNCTION INPUT ALARM - once time i7 has passed the display will show the flashing code “iA” and the buzzer
will be activated (until the input is disactivated)
4 = ACTIVATION OF THE PRESSURE SWITCH ALARM - the compressor will be switched off, if u1 and/or u11 = 6 the condenser fan will be
switched on, the display will show the flashing code “iA” and the buzzer will be activated (until the input is disactivated): when the
input has been activated the number of times established with parameter i8 the regulators will be switched off, if u1 and/or u11 = 6
the condenser fan will be switched on, the display will show the flashing code “iSd” and the buzzer will be activated (until the input
is disactivated and the instrument is switched off and re-started or until the power supply is interrupted); see also i7 and i9
5 = SWTICHING ON THE AUXILIARY OUTPUT - the auxiliary output will be switched on (only if u1 and/or u11 = 2, until the input is
disactivated)
6 = SWITCHING OFF THE INSTRUMENT - the instrument will be switched off (until the input is disactivated)
type of mutlifunction input contact
0 = normally open (active input with closed contact)
1 = normally closed (active input with open contact)
if i5 = 3, multifunction input alarm delay (code “iA”)
if i5 = 4, delay in compressor switching on after the disactivation of the multifunction input (21)
number of multifunction input alarms (code “iA”) such to cause a pressure switch alarm (code “iSd”) (if i5 = 4)
0 = alarm absent
time that must pass in absence of mutlifunction output alarms (code “iA”) so that the alarm counter is reset (only if i5 = 4)
time without activations of the door switch input (on condition that the cabinet temperature has reached the working setpoint) in order
that function Energy Saving is activated automatically (it has effect on the evaporator fan only if F0 = 1 or 2)
0 = the function will never automatically be activated
minimum time the door switch input must be activated such as to provoke the exclusion of the consequent value of the evaporator
temperature among the ones used for the calculation of the relative average (for the defrost activation; only if d8 = 3); also look at d17
minimum time the door switch input must be activated altogether such as to provoke the exclusion of the consequent value of the
evaporator temperature among the ones used for the calculation of the relative average (for the defrost activation; only if d8 = 3); also look
at d17
number of door switch input activations such as to provoke the defrost activation
0 = the defrost will never be activated because of the door switch input activation
minimum duration of the door switch imput activation such as to provoke the defrost activation
0 = the defrost will never be activated because of the door switch input activation
DIGITAL OUTPUTS
operation controlled by fourth output (22)
0 = CELL LIGHT - in this case the AUXILIARY key and parameters i0 and u2 will be activated
1 = DEMISTER RESISTORS - in this case the AUXILIARY key and parameter u6 will be activated
2 = AUXILIARY OUTPUT - in this case the AUXILIARY key and parameters i5 and u2 will be activated
3 = ALARM OUTPUTS - in this case parameter u4 will be activated
4 = DOOR RESISTORS - in this case parameter u5 will be activated
5 = EVAPORATOR VALVE - in this case parameters u7 and u8 will be activated
6 = CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated
enabling of manual switch on/switch off of the cell light or the auxiliary output when the instrument is switched off
(only if u1 and/or u11 = 0 or 2) (23)
1 = YES
enabling of alarm output disactivation with the silencing of the buzzer (only if u1 and/or u11 = 3)
1 = YES
cell temperature below that at which the door resistors are switched on (“u5 - 2.0 °C/4 °F, only if u1 and/or u11 = 4) (6)
operating time of demistor resistors (only if u1 and/or u11 = 1)
cell temperature below that at which the evaporator valve is disactivated (relating to the working setpoint, that is “working setpoint + u7”)
(only if u1 and/or u11 = 5) (6)
type of evaporator valve contact (only if u1 and/or u11 = 5)
0 = normally open (valve active with contact closed)
1 = normally closed (valve active with contact open)
enabling of buzzer
1 = YES
operation controlled by fifth output (22)
0 = CELL LIGHT - in this case the AUXILIARY key and parameters i0 and u2 will be activated
1 = DEMISTER RESISTORS - in this case the AUXILIARY key and parameter u6 will be activated
2 = AUXILIARY OUTPUT - in this case the AUXILIARY key and parameters i5 and u2 will be activated
3 = ALARM OUTPUTS - in this case parameter u4 will be activated
4 = DOOR RESISTORS - in this case parameter u5 will be activated
5 = EVAPORATOR VALVE - in this case parameters u7 and u8 will be activated
6 = CONDENSER FAN - in this case parameters P4, F11 and F12 will be activated
ENERGY SAVING IN REAL TIME
time of activation of the Energy Saving in real time function; see also r4 and HE2
duration of the Energy Saving in real time function; see also r4 and HE1
00:00= the Energy Saving in real time function will not be activated
DEFROSTING IN REAL TIME
time of activation of first defrosting period in real time (only if d8 = 4)
- - : - - = the first defrosting in real time will not be activated
time of activation of second defrosting period in real time (only if d8 = 4)
- - : - - = the second defrosting in real time will not be activated
time of activation of third defrosting period in real time (only if d8 = 4)
- - : - - = the third defrosting in real time will not be activated
time of activation of fourth defrosting period in real time (only if d8 = 4)
- - : - - = the fourth defrosting in real time will not be activated
time of activation of fifth defrosting period in real time (only if d8 = 4)
- - : - - = the fifth defrosting in real time will not be activated
time of activation of sixth defrosting period in real time (only if d8 = 4)
- - : - - = the sixth defrosting in real time will not be activated
SERIAL NETWORK (MODBUS)
instrument address
baud rate (0 = 2,400 baud, 1 = 4,800 baud, 2 = 9,600 baud, 3 = 19,200 baud)
parity (0 = none, 1 = odd, 2 = even)