Isdu read/write object definition (74 hex), Class attributes, Instance attributes – Comtrol IO-Link Master EIP-4 User Manual
Page 43: Common services

IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A
Chapter 3. EtherNet/IP CIP Object Definitions - 43
ISDU Read/Write Object Definition (74 hex)
All PDO data is received and returned in the configured PDO format (8-bit, 16-bit or 32-bit). Refer to
(Process Data Output) Transfer Object Definition (73 hex)
on Page 42 for a detailed explanation of the PDO
data block.
3.4. ISDU Read/Write Object Definition (74 hex)
The ISDU Read/Write object defines the attributes by which the PLC can:
•
Send an ISDU request containing one or more read and/or write ISDU commands to an IO-Link device
via the IO-Link Master.
•
Request the ISDU response(s) from the IO-Link Master.
•
Send both blocking and non-blocking ISDU requests.
Refer to the ISDU Handling chapter for a detailed description of the ISDU functionality.
3.4.1. Class Attributes
The following table shows the Class Attributes for the ISDU Read/Write Object Definition (74 hex).
3.4.2. Instance Attributes
The following table shows the Instance Attributes for the ISDU Read/Write Object Definition (74 hex).
3.4.3. Common Services
The following table shows the Common Services for the ISDU Read/Write Object Definition (74 hex).
Attribute ID
Name
Data Type
Data Value(s)
Access Rule
1
Revision
UINT
1
Get
2
Max Instance
UINT
4
Get
3
Num Instances
UINT
4
Note: Instance number determines IO-
Link port on the IO-Link Master.
Get
Attribute ID
Name
Data Type
Data Value(s) Access Rule
1
ISDU Response
ISDU response data block
0-255
Get
2
ISDU Read/Write Request
ISDU request data block
0-255
Set
Service Code Implemented in Class
Implemented in Instance
Service Name
01 hex
Yes
No
Get_Attributes_All
0E hex
Yes
Yes
Get_Attribute_Single
10 hex
No
Yes
Set_Attribute_Single
02 hex
No
No
Set_Attribute_All