Plc-5 and slc messages – Comtrol IO-Link Master EIP-4 User Manual
Page 105

IO-Link Master EtherNet/IP Reference Manual: 2000589 Rev. A
Chapter 7. SLC/PLC-5/MicroLogix Interface - 105
PLC-5 and SLC Messages
•
PLC-5 Programmable Controllers System Selection Guide, Rockwell Publication 1785-SG001A-EN-P
•
Ethernet Interface Module Series B, Revision D Product Release Notes, Rockwell Publication 1785-
RN191E-EN-P
Note: Older versions of firmware may or may not provide Ethernet/IP functionality.
7.3. PLC-5 and SLC Messages
The following PCCC messages are supported for the PLC-5 and SLC 5/05 PLCs.
The Receive Port Information is provided in one continuous file. The following file addresses are used to
retrieve the various parameters.
Message Type
PCCC Message ID
Maximum Message Size
Maximum Serial Packet Size
SLC Typed
Read
162
CLX: 242 SINTs (121 INTs)
SLC: 206 SINTs (103 INTs)
PLC-5: 240 SINTs (120
INTs)
CLX: 238 SINTs (119 INTs)
SLC: 202 SINTs (101 INTs)
PLC-5: 236 SINTs (118 INTs)
SLC Typed
Write
170
CLX: 220 SINTs (110 INTs)
SLC: 206 SINTs (103 INTs)
PLC-5: 238 SINTs (119
INTs)
216 SINTs (108 INTs)
SLC: 202 SINTs (101 INTs)
PLC-5: 234 SINTs (117 INTs)
PLC-5 Typed
Read
104
CLX: 234 SINTs (117 INTs)
SLC: 252 SINTs (126 INTs)
PLC-5: 238 SINTs (119
INTs)
230 SINTs (115 INTs)
SLC: 248 SINTs (124 INTs)
PLC-5: 234 SINTs (117 INTs)
PLC-5 Typed
Write
103
CLX: 226 SINTs (113 INTs)
SLC: 226 SINTs (113 INTs)
PLC-5: 224 SINTs (112
INTs)
CLX: 222 SINTs (111 INTs)
SLC: 222 SINTs (111 INTs)
PLC-5: 220 SINTs (110 INTs)
IO-Link
Port 1
IO-Link
Port 2
IO-Link
Port 3
IO-Link
Port 4
Access
Length
PDI Data Block
N10:0
N20:0
N30:0
N40:0
Read-Only
Configurable per port
Note: See the table
below for details.
Receive PDO
Data Block
N11:0
N21:0
N31:0
N41:0
Read-Only
Configurable per port
Note: See the table
below for details.
Transmit PDO
Data Block
N12:0
N22:0
N32:0
N42:0
Write-
Only
Configurable per port
Note: See the table
below for details.
Receive ISDU
Response
N13:0
N23:0
N33:0
N43:0
Read-Only
4 INTs to Max Msg Size
Transmit ISDU
Request
N14:0
N24:0
N34:0
N44:0
Write-
Only
4 INTs to Max Msg Size
Port Information Block (Continuous Block)
464 Bytes
(232 INTs)