Comtrol IOLM 4-EIP User Manual
Page 39
IO-Link Master 4-EIP User Guide: 2000582 Rev. A
Chapter 5. IO-Link Port Configuration - 39
EtherNet/IP Settings Parameters
Maximum PLC Update Rate
Default: 40ms
The maximum rate at which the IO-Link Master updates the PDI tag or
file.
This parameter is used to ensure that the PLC receives all state changes.
Setting the update rate to 10 ms effectively disables this feature. The
valid range is 10 to 65535 ms.
Heartbeat Update Enable
Default: False
If selected, the IO-Link Master updates the PDI data block at the
Heartbeat Update Rate.
•
False = Heartbeat update disabled
•
True = Heartbeat update enabled
Heartbeat Update Rate
Default: 1000ms
If Heartbeat Update Enable is selected, the rate at which the IO-Link
Master updates the PDI data block in the Write-to-Tag/File mode.
The valid range is 50 to 65535 ms.
Read PDO from Tag/File Settings
PDO Tag/File Name
Default: blank
The tag or file name that the IO-Link Master reads the PDO data block
from.
•
ControlLogix family:
-
Tags must be same type as PDO Data Format (SINT, INT or
DINT).
-
Tags must be an array.
-
Tags must be at least as long as the PDO Data Block Length.
•
SLC/PLC-5/MicroLogix:
-
Files must be of INTEGER (16-bit) type.
-
Files must be named with standard file name conventions (i.e:
N10:0, N21:30, etc)
The file must be at least as long as the PDO Data Block Length.
PLC Poll Rate
Default: 1000ms
The frequency which the IO-Link Master reads the PDO data block in the
Read-from-Tag/File mode.
Valid range: 50-65535 ms
EtherNet/IP Settings Page (Continued)