Chapter 5. IO-Link Port Configuration
IO-Link Master 4-EIP User Guide: 2000582 Rev. A
EtherNet/IP Settings Parameters
Transfer Mode Settings
PDI Receive Mode(s)
Default: Polling, Class1
Determines which PDI Receive (To PLC) Modes are enabled. Supported
modes are:
•
Polling
•
Class1
•
Write-to-TagOrFile
PDO Transmit Mode
Default: Class 1
Supported modes are:
•
Off
•
PLC-Writes
•
Class1
•
Read-from-TagOrFile
Read/Write Tag/File Settings
PLC IP Address
Default: 0.0.0.0
The PLC IP Address is required if either Write-to-TagOrFile or Read-from-
TagOrFile mode are enabled.
Format: xxx.xxx.xxx.xxx
PLC Controller Slot Number
Default: 0
The PLC Controller Slot Number is required if either Write-to-TagOrFile
or Read-from-TagOrFile mode are enabled.
Valid range: 0-64
PLC Type
Default: ControlLogix
Indicates the type of PLC that the tag(s) or file(s) are written to and/or
read from. Supported PLC Types are:
•
ControlLogix
•
SLC
•
PLC-5
•
MicroLogix
Write PDI to Tag/File Settings
PDI Tag/File Name
Default: blank
The tag or file name to place the PDI data block.
•
ControlLogix family:
-
Tags must be same type as PDI Data Format (SINT, INT or DINT).
-
Tags must be an array.
-
Tags must be at least as long as the PDI Data Block Length.
•
SLC/PLC-5/MicroLogix:
-
Files must be of INTEGER (16-bit) type.
-
Files must be named with standard file name conventions (i.e:
N10:0, N21:30, etc)
-
The file must be at least as long as the PDI Data Block Length.
Append PDO to PDI Data
Default: False
If selected, the IO-Link Master appends any PDO data to the end of the
PDI data.
•
False = Do not append PDO data
•
True = Append PDO data
EtherNet/IP Settings Page (Continued)