LEAVING WATER

SUCTION

\

INLET

COOLER TUBE

CONNECTION

THERMISTOR..

ENTERING COOLER

WATER SENSOR

Fig. 4

Cooler Sensor Locations

Thermistors mis-located or out of

calibration.
Code 68 and 69, Low Suction Superheat

if the follow-

ing logic is satisfied, then all the compressors on the
circuit

be stopped.

Suction superheat is equal to 0°F

or the satu-

rated suction is greater than 58 F (14.4 C) and either
condition has been true for more than 5 minutes.

Possible causes for this failure are a stuck electronic

expansion valve or thermistors mis-located or out of
calibration.

To reset, use the manual reset method.

Code 71 to 81, Thermistor Failure

If the measured

temperature of a thermistor is less than

F (-51 C)

(363,000 ohms) or greater than 240 F (116 C) (2 16 ohms),

the appropriate sensor error code will be displayed and
the unit

be stopped. The thermistor failures will

automatically reset. The following is a summary of

possible causes.

Thermistor Failure

A shorted or open circuit ther-

mistor will cause the failure.

Wiving Failure

A shorted or open circuit will cause

the failure.

Module

If the circuitry in the pro-

cessor module fails, the error could occur.

NOTE: The reset thermistor is an optional thermistor

and is only used with outside or space temperature reset.

It will only be read by the processor if the unit is con-

figured for outside or space temperature reset.

The absence of a thermistor failure does not necessarily

mean that a thermistor is accurate. To determine
accuracy, the reading must be compared with a measure-

ment of the actual temperature to which the thermistor

probe is exposed.

Quick Test

The Quick Test feature allows the service

technician to individually test all the inputs and outputs
of the control system.

The test function operates the Quick Test diagnostic

program. When the unit is in STANDBY mode, the test
subfunctions will energize the solenoid valves, unloaders,
electronic expansion valves and compressors. The
solenoids and unloaders will energize for 3 minutes. The
electronic expansion valve

travel to fully open in one

test and to fully closed in the next. The compressors
energize for 10 seconds. The subfunctions are explained
below. Refer to Table 6 for all the elements in the
subfunctions.

NOTE: The Quick Test energizes the alarm light and

alarm relay. They will remain energized as long as the unit
is in Quick Test.

To reach a particular test, enter its subfunction number

and then scroll to the desired test with the

key. A

test can be terminated by pressing

c

l

. Pressing

after a test has started will advance the system to the
next test, whether the current one is operating or has
timed out. Once in the next step, you may start the test

by pressing

or advance past it by pressing .

c

l

c

l

While the unit is in Quick Test, you may access another

display or function by depressing the appropriate keys;

however, the unit will remain in the Quick Test func-

tion until

is entered, or, if the keyboard is

not used for 10 minutes, the unit will automatically leave
the Quick Test function. See the following example: