beautypg.com

Damper wiring, Thermostat wiring, Conventional thermostats – Braeburn 140424 User Manual

Page 7

background image

Damper Wiring

3.1

Install the system dampers using the instructions provided by the manufacturer.
Connect the dampers to the zone panel expander as shown for either a 2-wire
or 3-wire damper. The sum of all dampers powered by the zone panel should
not exceed 75 VA at 24 VAC. Use a slave relay if additional damper power
is required.
ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED

M
M

PO

COM

PC

Zone Panel

2-Wire Damper

PO
C
PC

PO

COM

PC

Zone Panel

3-Wire Damper

7

Thermostat Wiring

3.2

1 HEAT / 1 COOL

R 24 VAC Power
W1 Heat Call
Y1 Cooling Call
G Fan Call

C

24 VAC Transformer Common

[Note 1]

2 HEAT / 2 COOL

R 24 VAC Power
W1 Heat Call Stage 1
W2 Heat Call Stage 2
Y1 Cooling Call Stage 1

Y2 Cooling Call Stage 2

G Fan Call

C 24 VAC Transformer Common

[Note 1]

3 HEAT / 2 COOL

R 24 VAC Power
W1 Heat Call Stage 1
W2 Heat Call Stage 2

W3 Heat Call Stage 3

Y1 Cooling Call Stage 1

Y2 Cooling Call Stage 2

G Fan Call

C 24 VAC Transformer Common

[Note 1]

CONVENTIONAL THERMOSTATS

NOTE: To prevent possible interference do not run low voltage
wiring along side 120 VAC wiring or magnetic ballasts.

NOTES

[1] Wiring to the C terminal is required only for thermostat power.