Add Zones to Main Panel

5

The 4 Zone Expandable Panel can be expanded to up to 32 zones with four zones on the main panel and 28
total expansion zones. Additional zones must have power and communication wires to be recognized and
controlled by the main expandable panel. To add additional zones, complete all wiring and start the main
panel test mode.

Start the panel test mode to add additional zones:

1. Ensure all wiring is complete, zone addresses are set (section 4),
and power has been applied to the main and expansion panels.
2. Press TEST for 3 seconds and release.
3. Press and release SELECT once for each new zone added.
New zones must be added in blocks of two.

NOTE: After second

new zone is added, expander LED will change from red to green,
and ZONE OK will appear in the main panel display.
4. If new zones do not appear, check wiring and ensure expansion
zones have power.
5. Press HOLD FOR EXIT for 3 seconds to complete adding zones.

Operation

6

The Zone Panel Expander has built in LED’s to tell the installer and the system owner the current operating
mode of the panel. Refer to the figure below and the following descriptions of the panel LED’s for operation
information.

10

LED

COLOR

INDICATION

Panel Status LED

Panel Power

Red

Flashing Red until communication is good

Green

Flashing Green when in normal operation

Thermostat LED’s (2 Positions)

R

Red

24 VAC available to Thermostat

Y1

Yellow

Thermostat First Stage Compressor Call

Y2

Yellow

Thermostat Second Stage Compressor Call

W1/E/AX1

White

Thermostat Call for W1 or E or AX1

W2/AX2

White

Thermostat Call for W2 or AX2

O/B/W3

Yellow

Thermostat Call for O, B or W3

G

Green

Thermostat Fan Call

L

Yellow

System Check Signal to Thermostat Active

Damper LED’s (2 Positions)

Power Close / Power Open

Red / Green

Red On Damper Closed; Green on Damper Open

No light when wiring short detected.