Verify green power LED near 24 VAC terminals is lit.

[ ]

Verify green heartbeat LED in middle of panel is pulsing.

[ ]

Verify all 3 zone LEDs near damper terminals are green.

[ ]

Verify supply temp display shows current plenum temperature.

[ ]

Switch zone 1 thermostat to heat mode, and call for heat in zone 1 by raising set

temperature above room temperature.

[ ]

Verify zone 1 damper LED stays green (open) and zone 2 and 3 damper LEDs change

to red (closed).

[ ]

Verify heating system is operating, air is moving out zone 1 vents, and zone 2 and 3

vents have minimal airflow.

[ ]

Verify supply temp display on zone panel shows a heat change in supply air.

[ ]

Switch zone 2 thermostat to heat mode, and call for heat in zone 2 by raising set

temperature above room temperature.

[ ]

Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to

green (open).

[ ]

Verify heating system is operating and air is moving out into zone 1 and zone 2.

[ ]

If installed, switch zone 3 thermostat to heat mode, and call for heat in zone 3 by raising

set temperature above room temperature. Verify air is now flowing to zone 3.

[ ]

If installed, verify emergency heat remote and panel switch. Return E-Heat switches to

normal position when test is complete.

[ ]

Return zone 1 thermostat to the off position. Verify zone 1 damper LED turns red and

zone 2 and 3 damper LEDs stay green.

[ ]

Verify heating system is operating, air is moving out zone 2 and 3 vents, and zone 1

vents have minimal airflow.

[ ]

Return zone 2 and 3 thermostats to the off position. Verify system fan shuts off at the end

of purge cycle.

[ ]

Verify all zone LEDs near damper terminals are green.

[ ]

If the outside temperature is acceptable, repeat the above steps in cooling mode.

Cooling will not work if E-Heat is on.

[ ]

Restore thermostats and replace J2 jumper if short cycle protection at zone panel

is required.