background image

4

Configuration

Use the following instructions to configure the Premier 3-Zone Controller.

1. Open J1 jumper for dual transformer installations.

2. Open J2 short cycle protection jumper for system test.

Note: Replace J2 when system testing is completed or leave J2 open if compressor has built in

short cycle protection.

3.

Press

▲ and then press ▲ to raise or ▼ to lower the Hi Temp cutout.

4.

Press

▼ and then press ▲ to raise or ▼ to lower the Low Temp cutout.

5. Press

▲ and ▼ at the same time to adjust purge time. Press ▲ to raise or ▼

to lower the

purge time.

Figure 4

6

RH
RC
Y1
Y2

G
G2

W1

AUX

W2

O/B

C

HI/LOW LIMIT

CUTOUT ADJUST

J2-SHORT CYCLE

PROTECTION

EQUIPMENT

Braeburn

3-Zone

JI REMOVE TO SEPARATE
RH AND RC TERMINAL

SUPPLY TEMP

HI TEMP

LO

TEMP

PURGE

DELAY

J2 jumper

J1 jumper

HI/LOW

temp cutout

adjustment