Installer Guide 4

1 HEAT / 1 COOL Single or Dual Transformer

Set System Type to 11CONV

Rh 24 Volt AC Power (heating transformer) [note 2]
Rc
24 Volt AC Power (cooling transformer) [note 2]
W1
Heat Relay
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

NOTES - Conventional Systems

[1] Optional 24 Volt AC common connection

(required for Wi-Fi).

[2] Remove factory installed jumper for dual

transformer systems.

[3] In dual transformer systems, transformer

common must come from cooling transformer.

[4] If needed for system.
Provide disconnect and overload protection

as required.

2 HEAT / 2 COOL Single or Dual transformer

Set System Type to 22CONV

Rh 24 Volt AC Power (heating transformer) [note 2]

Rc 24 Volt AC Power (cooling transformer) [note 2]

W1 Heat Relay Stage 1
W2 Heat Relay Stage 2
Y1 Compressor Relay Stage 1
Y2 Compressor Relay Stage 2 [note 4]
G
Fan Relay
C 24 Volt AC Transformer Common [note 1, 3]

Typical Wiring Configurations

NOTE: The “System Type” option will be configured in the Installer Settings section.

Conventional Systems

Heat Only

Set System Type to 11CONV

Rh 24 Volt AC Power
W1 Heat Relay

G Fan Relay [note 4]

C 24 Volt AC Transformer Common [note 1]