beautypg.com

Braeburn 7320 Installer Guide User Manual

Page 13

background image

13 Installer Guide

25 Economizer, Fresh Air or Output Control [note 11] – Selects control options. Select between disabled

(NONE), economizer mode (ECON) and time of day (TOD) mode.

26 Heat Set Point Upper Limit – Selects the heating set point upper adjustment limit.

27 Cool Set Point Lower Limit – Selects the cooling set point lower adjustment limit.
28 Humidification Mode [note 12] – For use with an external humidifier. Selects between disabling

humidification (OFF), dependent control (DEP) or independent control (IND). The DEP setting controls

humidification only during a call for heating. The IND setting allows humidification output in the heat mode,

but does not require a call for heating.

NOTE: It is recommended that the IND setting only be used with

systems designed for low air temperature humidification such as steam humidification. Always ensure the

heat exchanger or other system parts are not exposed to excess water from condensation or other sources.

When there is any doubt, use the OFF or DEP setting.

29 Auto Humidity Set Point Limit [notes 10, 12] – Select between turning the automatic

humidity set point limit to auto (AUTO) or manual (MAN). When AUTO is selected, humidity control is provided

automatically based on the outdoor temperature. Selecting MAN allows you to manually control the level

of humidity.

30 Dehumidification [note 12] – For use with an external dehumidifier. Select between dehumidification

disabled (OFF), a normally inactive (NI) or normally active (NA) relay, depending on the requirements of your

external dehumidification equipment.

31 Installer Clear – Clears settings based on your selection. CLRO makes no changes, CLR1 clears all wireless

remote sensor settings and CLR2 clears

ALL thermostat settings to factory default.

WARNING: If you press NEXT or RETURN after selecting CLR1 or CLR2 the clear will take place and

the appropriate settings will be returned to factory defaults. If you do not wish to make any changes, use the

SpeedBar

®

to select CLRO.

Time Step / Override

Cooling Call

Occupied

YES or NO

ON

ON

OFF

YES

ON

OFF

OFF

NO

OFF

OFF

OFF

Override

YES or NO

ON

ON

OFF

External Air or Output Control (A)
Economizer Time of Disabled
Mode

Day Mode

Time Step / Override

Heating Call

Occupied

YES or NO

ON

ON

OFF

YES

OFF

OFF

OFF

NO

OFF

OFF

OFF

Override

YES or NO

ON

ON

OFF

External Air Output (A)
Economizer Time of Disabled
Mode

Day Mode

Unoccupied

Unoccupied