Table 3-8. Relationship Between Air/Fuel Valve Position and Energy Input For

Unit Running On Natural Gas

Air/Fuel Valve Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0

0

0

10%

0

0

18%

(Stop Level)

100,000

5.0%

20%

134,000

7%

30%

349,000

17%

40%

631,000

32%

50%

893,000

45%

60%

1,150,000

58%

70%

1,410,000

71%

80%

1,610,000

81%

90%

1,830000

92%

100%

2,000,000

100%