Table A-1: Boiler Menu Item Descriptions-Continued
MENU LEVEL & OPTION
DESCRIPTION
COMBUSTION CAL MENU
CAL Voltage 18% or
Cal Voltage 20%
Allows for the selection of the Blower Motor output
voltage at 18% (Natural Gas), or 20% (Propane)
CAL Voltage 30%
Allows for the selection of the Blower Motor output
voltage at 30% (Natural Gas or Propane)
CAL Voltage 45%
Allows for the selection of the Blower Motor output
voltage at 45% (Natural Gas or Propane)
CAL Voltage 60%
Allows for the selection of the Blower Motor output
voltage at 60% (Natural Gas or Propane)
CAL Voltage 80%
Allows for the selection of the Blower Motor output
voltage at 80% (Natural Gas or Propane)
CAL Voltage 100%
Allows for the selection of the Blower Motor output
voltage at 100%(Natural Gas or Propane)
Set Valve Position
Allows for setting of VALVE POSITION (% Open).
Blower Output
Allows for the monitoring of Blower Output Voltage.
Set Stdby V Out
The Blower Motor remains “ON” in STANDBY Mode.
The motor speed is defined by setting this parameter to
a value of 0.00 Volts.