GF-123

Benchmark 2.0LN Low NOx Boiler

Chapter 3

OMM-0046_0F

I

nstallation, Operation and Maintenance Manual

Operation

PR1 10/17/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 43 of 172

Table 3-6: Combustion Cal Menu – Natural Gas

Table 3-7: Combustion Cal Menu – Propane

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

CAL Voltage 18%

.25

10.0v

1.00v

CAL Voltage 30%

.25

10.0v

2.30v

CAL Voltage 45%

.25

10.0v

2.95v

CAL Voltage 60%

.25

10.0v

3.60v

CAL Voltage 80%

.25

10.0v

5.30v

CAL Voltage 100%

.25

10.0v

9.10v

SET Valve Position

0%

100%

0%

Blower Output

Monitor Blower Output

Voltage

.00v

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

CAL Voltage 20%

.25

10.0v

1.10v

CAL Voltage 30%

.25

10.0v

1.95v

CAL Voltage 45%

.25

10.0v

3.00v

CAL Voltage 60%

.25

10.0v

3.00v

CAL Voltage 80%

.25

10.0v

4.45v

CAL Voltage 100%

.25

10.0v

8.20v

SET Valve Position

0%

100%

0%

Blower Output

Monitor Blower Output

Voltage

.00v