beautypg.com

Cntby – Kistler-Morse KM Weigh II User Manual

Page 22

background image

4-2

Chapter 4. Display

Follow this procedure to modify the averaging
factor.

1. If the Weigh II is in Auto Mode (Auto LED

illuminated), press the Auto/Man Key to
put the system in Manual Mode. The Auto
LED turns off.

2. Use the Up Arrow or Down Arrow Keys to

scroll to the desired channel.

3. Press the Menu Key to display the Main

Menu. The display shows:

4. Press the F1 Key to access the Display

Menu. The display shows:

5. Press the F1 Key to access the Avg

Menu. The display looks like this:

In place of ‘X’ is the current averaging
factor.

6. Use the keypad or the Up and Down Arrow

Keys to input the value for the averaging
factor. Press the Enter Key to save the
value in memory. The display flashes a
message acknowledging your selection
and returns to:

7. Press the Esc Key to scroll up the menu

tree or press the Auto/Man Key to return
the display to vessel monitoring.

Cntby

This menu is used to set up the display to
count by increments of 1, 2, 5, 10, 20, 50,
100, 200, 500, 1000, 5000, or 10000. For
example, a Cntby of 1 would show the
rightmost active digit on the display changing
by increments of 1. A Cntby of 100 would
show the rightmost three active digits on the
display changing by increments of 100 units.
Use Cntby to adjust the display to a resolu-
tion consistent with the accuracy of the
system and reduce display flickering.

Example: For a 10,000 lb maximum weight
with a Form of XXXXX, a Cntby of 1 would only
be meaningful if your system accuracy was
+/-.01% of maximum load. A more typical
accuracy would be +/-3%. Since 3% of
10,000 lbs is 300 lbs, a more realistic Cntby
for this system would be 200.

Note that the selection for Form affects how
the Weigh II interprets the Cntby value.
Table 4-1 shows some examples of how
these are related.

Form

Cntby

Example Value

(incremented digit

underlined)

xxx.xx

1

397.25

xxx.xx

100

397.00

xxxxx

1

39725

xxxxx

100

39700

xxxxxoo

1

3972500

xxxxxoo

100

3970000

Table 4-1. Interaction of Form and Cntby

The default value for Cntby is 1. The current
selection is indicated by an asterisk. The
Cntby function only affects the value seen on
the display. Setpoints, current outputs, and
serial outputs are unaffected by Cntby.

Follow this procedure to modify Cntby.

1. If the Weigh II is in Auto Mode (Auto LED

illuminated), press the Auto/Man Key to
put the system in Manual Mode. The Auto
LED turns off.

2. Use the Up Arrow or Down Arrow Keys to

scroll to the desired channel.

3. Press the Menu Key to display the Main

Menu. The display shows:

4. Press the F1 Key to access the Display

Menu. The display shows:

WII MAIN MENU

Disp I/O Cal

F1 F2 F3

DISPLAY MENU

Avg Cntby Units

F1 F2 F3

AVERAGE FACTOR

> X

F1 F2 F3

DISPLAY MENU

Avg Cntby Units

F1 F2 F3

WII MAIN MENU

Disp I/O Cal

F1 F2 F3

DISPLAY MENU

Avg Cntby Units

F1 F2 F3