Parameters of Commands and Responses

*5

The data number “008” can be read to check the error status of the sensor amplifiers.
Convert the five digit number (ASCII characters) read from the sensor amplifiers to a binary
number and check the ON/OFF state of each bit to
check the error contents.

For information on each error, refer to "FD-S Series User's Manual".

• When the data read from a sensor amplifier is "1056":

"1056" converted to binary number is "0000 0100 0010 0000".

Therefore, this data indicates that the "temperature low error" and the "reverse
current error" have occurred at the same time on the sensor amplifier from which the
data was read.

• If no error has occurred at the sensor amplifier, the data "0000" is returned.

*6

When the data falls below 0, this indicates "-999.9", and when the data exceeds 99.9, this
indicates "+999.9".

Bit

Error contents of sensor amplifiers

0

Not used

1

Head connection error (ErH)

2

Overcurrent error (ErC)

3

EEPROM error (ErE)

4

Empty pipe error (Erd)

5

Reverse current error (rEv)

6

Not used

7

Not used

8

Not used

9

Drive gain error

10

Temperature low error

11

Temperature high error

12 to 15

Not used

Reference

Bit 10: Temperature low error

Bit 5: Reverse current error

Parameters of Commands and Responses

Read/write data

The following table lists the types of data that can be read from and written to FD-S Series sensor amplifiers.

Data

number

Data name

Data format

*1

Data range

0.2L

1L, 2L

8L, 20L

0.2L

1L

2L

8L

20L

020

Integrated flow reset request

*

0: Disable integrated flow reset

*3

1: Integrated flow reset

Lead: Last written value

021

Instantaneous flow hold value
reset request

0: Disable hold reset

*3

1: Hold reset

Lead: Last written value

022

Temperature hold value reset
request

0: Disable temperature hold reset

*3

1: Temperature hold reset

Lead: Last written value

023

Zero adjustment request

0o1: Perform zero adjustment

*4

024

Request initial reset (SLct)

0o1: Conduct initial reset (SLct)

030

Instantaneous flow rate setting 1

***.*

****

**.**

000.0 to

400.0

*5

0000 to

2000

*5

0000 to

4000

*5

00.00 to

16.00

*5

00.00 to

40.00

*5

031

Instantaneous flow rate setting 2

032

Instantaneous flow rate setting 3

033

Instantaneous flow rate setting 4

034

Integrated flow quantity setting 1

****

0000 to 9999

035

Integrated flow quantity setting 2

036

Temperature setting lower limit

***.*

000.0 to 099.9

*6

037

Temperature setting upper limit

000.1 to 100.0

*7

038

Specified density for voL.S

****

0300 to 2000

040

Detection mode

*

0: F-1
1: F-2
2: F-3
3: A-1
4: A-2

041

Integration direction

0: Increment

1: Decrement

042

Time-out time for output 2
(unit: s)

**

1 to 99

043

Output mode

*

Bit0: Output1 (1: N.C.)
Bit1: Output2 (1: N.C.)
Bit2: Output3 (1: N.C.)

044

Integrated flow quantity unit
(Original Method)

1: 0.1

2: 1

3: 10

4: 100

5: 1000

7: (1L(Foc) is

fixed to 7)

7: Fixed

2: 1

3: 10

4: 100

5: 1000

6: 10000

7: (8L(Foc) is

fixed to 7)

7: Fixed

0: 0.01

1: 0.1

2: 1

3: 10

4: 100

045

Response time

0: 0.05s

1: 0.1s
2: 0.5s
3: 1.0s
4: 2.5s
5: 5.0s

6: 10.0s
7: 30.0s
8: 60.0s

046

Display mode

0: Std

1: rESo

047

Hysteresis

***.*

****

**.**

000.0 to

200.0

0000 to 1000 0000 to 2000

00.00 to

08.00

00.00 to

20.00

048

Input terminal function

*

0: OFF

1: Bank switching

2: Flow rate zero

3: Zero adjustment
4: Integration reset

049

Flow indicator color (Can set
at 1L or 8L, however ignore)

0: Red for ON, green for OFF

1: Green for ON, red for OFF

050

Power save mode

0: OFF

1: ON

2: FULL

051

Analog output selection

0: Standard

1: Free range analog