beautypg.com

Parameters of commands and responses, Coriolis digital flow sensor fd-s series – KEYENCE DL-RS1A/FD-S User Manual

Page 12

background image

10

Parameters of Commands and Responses

This section describes the parameters used with various commands and responses.

Coriolis Digital Flow Sensor FD-S Series

Communication commands

There are two types of communication commands: read commands and write commands.

ID numbers

This parameter is used with communication commands "SR" and "SW". Specify the ID number of the
target sensor amplifier using two digits (ASCII characters).
Example: Sensor amplifier of ID number 00 = 00, sensor amplifier of ID number 02 = 02

Communication

command

Attribute

Description

SR

Read

Reads the data for the specified data number from the sensor amplifier with the

specified ID number.

M0

Reads all of the instantaneous flow rate (current value) data that DL-RS1A

periodically retrieves from all sensor amplifiers.

MS

Reads the control output state and instantaneous flow rate (current value) data

that DL-RS1A periodically retrieves from all sensor amplifiers.

DR

Reads the control output state and instantaneous flow rate (current value) data

that DL-RS1A periodically retrieves from all sensor amplifiers when a DRQ input

is received.

SW

Write

Writes setting data for the specified data number into the sensor amplifier with

the specified ID number.

AW

Writes setting data for the specified data number into all sensor amplifiers.

Parameters of Commands and Responses

Data numbers

Specify the data number using three digits (ASCII characters).

Read-only data

The following table lists the types of data that can only be read from FD-S Series sensor amplifiers.

Writing read-only data results in a communication error (error number: 22).

*1

In the Data format column, "*" signifies a number from "0 to 9".

*2

R: Indicates that the data type can only be read from the sensor amplifiers.

*3

Regardless of the display mode setting specified on the sensor amplifier, this is the data during
the “rESo” mode.

*4

Regardless of the integration display unit specified on the sensor amplifiers, the data is read
with the minimum display unit.
When the integrated flow quantity exceeds the indicated maximum value, the maximum value is
returned as the data.

Data

number

Data name

Data format

*1

Data range

0.2L

1L, 2L

8L, 20L

0.2L

1L

2L

8L

20L

000

Instantaneous
flow rate

±***.*

±****

±**.**

-400.0 to
+400.0

*2

-2000 to

+2000

-4000 to

+4000

-16.00 to

+16.00

-40.00 to

+40.00

001

Integrated flow
quantity
(Original Method)

±********.*

±*********

±*******.**

-21474836.4 to
+21474836.4

*4

-214748364 to

+214748364

-2147483.64 to

+2147483.64

002

Instantaneous
flow rate
(peak hold value)

±***.*

±****

±**.**

-400.0 to
+400.0

*3

-2000 to

+2000

-4000 to

+4000

-16.00 to

+16.00

-40.00 to

+40.00

003

Instantaneous
flow rate
(bottom hold
value)

-400.0 to
+400.0

*3

-2000 to

+2000

-4000 to

+4000

-16.00 to

+16.00

-40.00 to

+40.00

004

Instantaneous
density

**.**

00.00 to 99.99

005

Output terminal
state

*

Bit0: output 1 (ON at 1)
Bit1: output 2 (ON at 1)
Bit2: output 3 (ON at 1)

006

Input terminal
state

0: OFF, 1: ON

007

Bank switching
state

0: bank A; 1: bank B

008

Error state

****

0 to 2604

*5

009

Connected
sensor head
(quality)

*

0: SUS
1: PFA

1: PFA

0: SUS
1: PFA

1: PFA

0: SUS

010

Connected
sensor head
(capacity)

0: 0.2L
1: 2L(Foc)
3: L(Foc)

3ÅF1L

1: 2L
2: 20L(Foc)
4: 8L(Foc)

4: 8L

2: 20L

011

Integrated flow
quantity
(Corresponding
to the A-Ver)

±********.**

±*********.*

±*******.***

-21474836.48 to

+21474836.47

-214748364.8 to

+214748364.7

-2147483.648 to

+2147483.647

015

Temperature
(current value)

±***.*

000.0 to 099.9

*6

016

Temperature
(peak hold value)

017

Temperature
(bottom hold value)

019

Shift system
processing results

*

0: normal termination; 1: abnormal termination

Point