Input table – Hardy HI 1769-FC User Manual
Page 47

42
●
●
●
●
●
Chapter 4
For the 5 pt Cal Type, you provide the five RateCal percents between the Low and High
output percentages.
For the advanced cal Type, you provide known flow rates for output percentage setpoints
(Pt2 and Pt4) and the output percentages. This only establishes the rate lookup table for
startup rates.
Input Table
.
The first 5 words of the input table echo the output table, except that the format word is
replaced with a command status that indicates whether a command succeeded or failed.
The next words are the OP% rate of change, the gross weight, rate setpoint, state, version,
and the module status word. There is also a counter which continuously increments.
Word
Offset
Description
CMD
0
Command # echo the command from the
input
CMD_STATUS
1
Status of command
PARAM_VALUE
2
Parameter value (LSW)
PARAM_VALUE
3
parameter value (MSW)
PARAM_NUMBER
4
Parameter number, in read and write
commands
OP
5
Operating %. 2 decimal places 0.00 -
100.00
ROC
6
Uses 'rate decimal places' ROC heavily
averaged value (LSW)
ROC
7
ROC heavily averaged value (MSW)
GROSS_WEIGHT
8
Uses 'weight decimal places' Gross wt.
(LSW)
GROSS_WEIGHT
9
Gross wt. (MSW)
RATESETPOINT
10
Uses ‘rate decimal places' Total . (LSW)