Chapter 4 Configuration
● ● ● ● ●
Chapter 4 covers the settings used to prepare the controller for calibration and operation.
The Setup procedures require Allen-Bradley’s RSLogix™ 5000, Allen-Bradley RSLinx®
or RSLinx® Lite for use in the CompactLogix™ system, or RSLogix 500 for the
MicroLogix™ 1500 system.
Power Check
To make or change settings,
there must be power to both the
PLC and the module. Verify that
the LED’s are lit for normal
operation.
Module LED’s
LEDS
Scale Data LED’s
Flashing Green
Feeder is on
Steady Green Running
(Normal)
Steady Red
Error Read Failure or Error eeprom write. Contact HI
Customer Support
Flashing Red
Read Convert Error.
LED is Off
Channel is Inactive
OK Module Status LED
Brief Steady
During power up the LED lights Red for about one second.
Flashing Green
In Program mode. (Normal)
Steady Green
In Run Mode. (Normal)
Steady Red
Config. Fault The eeprom checksum failed - bad serial
eeprom
(Backplane Available)
Data or blank serial eeprom. Contact HI Customer Support.
Steady Red
Internal Hardware watchdog timer fault (e.g. bad Hardware
or Firmware). ASIC is non-operational.
Flashing Red
Communication Error.