beautypg.com

Pilz PNOZ s8 C 24VDC 2 n/o User Manual

Page 8

background image

PNOZ s8

Operating Manual PNOZ s8
21400-EN-07

8

Relay outputs

750108

751108

Max. short circuit current IK

1 kA

1 kA

Utilisation category

In accordance with the standard

EN 60947-4-1

EN 60947-4-1

Safety contacts, AC1 at

240 V

240 V

Max. current

3,0 A

3,0 A

Min. current

0,02 A

0,02 A

Max. power

720 VA

720 VA

Safety contacts, DC1 at

24 V

24 V

Max. current

3,0 A

3,0 A

Min. current

0,02 A

0,02 A

Max. power

72 W

72 W

Utilisation category

In accordance with the standard

EN 60947-5-1

EN 60947-5-1

Safety contacts, AC15 at

230 V

230 V

Max. current

1,5 A

1,5 A

Safety contacts, DC13 (6 cycles/

min) at

24 V

24 V

Max. current

1,5 A

1,5 A

Contact fuse protection, external

safety contacts

In accordance with the standard

EN 60947-5-1

EN 60947-5-1

Blow-out fuse, quick

4 A

4 A

Blow-out fuse, slow

2 A

2 A

Circuit breaker, 24V AC/DC,

characteristic B/C

2 A

2 A

Contact material

AgSnO2

AgSnO2

Conventional thermal current

while loading several contacts

750108

751108

Ith per contact at UB DC

Conv. therm. current with 1 con-

tact

3,00 A

3,00 A

Conv. therm. current with 2 con-

tacts

3,00 A

3,00 A

Times

750108

751108

Switch-on delay

With automatic reset after power

on typ.

100 ms

100 ms

With automatic reset after power

on max.

150 ms

150 ms

Delay-on de-energisation

With E-STOP typ.

30 ms

30 ms

With E-STOP max.

40 ms

40 ms

With power failure typ.

30 ms

30 ms

With power failure max.

40 ms

40 ms