PNOZ s1

Operating Manual PNOZ s1
21393-EN-07

4

Safety features

The relay meets the following safety requirements:

}

The circuit is redundant with built-in self-monitoring.

}

The safety function remains effective in the case of a component failure.

}

The correct opening and closing of the safety function relays is tested automatically in

each on-off cycle.

}

The unit has an electronic fuse.

Block diagram/terminal configuration

Input

A1 A2

=

Power

Reset/

Start

S34

=

Y32

K1

K2

13 23

24

14

Interface expansion

unit

Centre: Front view with cover, right: Front view without cover

Function description

}

Single-channel operation: no redundancy in the input circuit, earth faults in the reset

and input circuit are detected.

}

Automatic start: Unit is active once the input circuit has been closed.

}

Manual reset: Unit is active once the input circuit is closed and then the reset circuit is

closed.

}

Increase in the number of available instantaneous safety contacts by connecting con-

tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.