Table 15 — Zone Air Balance/Commissioning Table

Heating Override — This variable can be used to test the heat
outputs. Enabling this variable will cause the heat to be modu-
lated or staged to full heat until this point is disabled or the
force released. Ducted reheat operation will be controlled so as
not to exceed the configured maximum duct temperature. The
supply-air temperature is included on this screen to verify that
the heat is operating.
Heating Override: Display Range

Dsable/Enable

Default Value

Dsable

Network Access Read /Write

Airflow CFM Set Point — This variable displays the current
airflow set point that the zone controller is controlling to. Dur-
ing the calibration tests this value can be forced, which will
change the set point configuration for the value being tested.
Airflow CFM
Set Point:

Display Units

CFM

Display Range

0 to 9999 (Limited by

velocity pressure transducer high alarm
limit)
Default Value

0

Network Access Read /Write

Actual Airflow Display — This variable shows the actual air-
flow being measured, based on the inlet size configured. Dur-
ing the Maximum and Minimum Cooling Airflow calibration
tests this value can be forced, which will correct the multiplier
or offset used to calculate the airflow.
Actual Airflow:

Display Units

CFM

Display Range

0 to 9999 (Limited by

velocity pressure transducer high alarm
limit)
Default Value

0

Network Access Read /Write

Primary Damper Position — This variable displays the cur-
rent damper position. During CFM Balancing, this variable is
used to display the position of the damper. This value can
be used to see if the damper is fully open and the system air is
sufficient.
Primary Damper
Position:

Display Units

% (open)

Display Range

0 to 100

Default Value

100

Network Access Read Only

Measured Velocity Pressure — This variable displays the
measured velocity pressure, which is used to check accuracy
during test and balancing of the terminal. If the pressure
appears to be much different than that measured with a Magna-
helic gage, the transducer can be forced to recalibrate its zero
by enabling the Damper/Transducer Calibration.
Measured Velocity
Pressure:

Display Units

in. wg

Display Range

0.000 to 2.000 (Limited

by velocity pressure transducer high alarm
limit)
Default Value

0.000

Network Access Read Only

Supply-Air Temperature — This variable displays the supply-
air temperature for ease of verifying the heat operation during
the heat test.
Supply-Air
Temperature:

Display Units

F (C)

Display Range

-40.0 to 245.0

Default Value

0.0

Network Access Read /Write

Auto-Calibration — This variable will display “Normal” if the
actuator and airflow transducer calibrations are successful. If
damper or transducer calibration was not successful, this point
will display “Alarm” and the zone controller will broadcast the
appropriate alarm (if configured to transmit alarms).
Auto-Calibration: Display Range

Normal/Alarm

Default Value

Normal

Network Access Read Only

Calibration Gain — Air terminal testing by industry standards
is done with straight duct, upstream of the terminal. Since most
applications are not installed in this manner, the actual airflow
from the terminal, at balancing, may not equal the reading from
the zone controller.

The Calibration Gain is used for making fine tuning adjust-

ments to the airflow calculation. This number is calculated au-
tomatically by the zone controller after input to the air balance
maintenance screen. The Calibration Gain can also be entered
manually in the service configuration CONFIG screen.

A number of .95 entered into the Calibration Gain variable

will cause the maximum airflow to be reduced to 95% of the
calculated value. A number of 1.05 would cause readings to
become 5% higher. The Calibration Gain is adjusted on the Air
Balance maintenance screen when performing the Maximum
Airflow Calibration and will have the greatest affect on the air-
flow at maximum CFM.

After performing the air balance procedure using the air bal-

ance maintenance screen, it is recommended to upload and
save the Airflow Configuration, Calibration Gain, and Offset
settings.
Calibration Gain: Display Range

0.000 to 9.999

Default Value

1.000

Network Access Read Only

DESCRIPTION

DEFAULT

POINT NAME

Commissioning Mode

Dsable

CMODE

Damper/Transducer Calibration

Dsable

CALIBRAT

Maximum Cooling

Dsable

MAXCOOL

Minimum Cooling

Dsable

MINCOOL

Heating Override

Dsable

HEATOVER

Fan Override

Dsable

FANOVER

CFM Set Point

0 cfm

COMCFM

Actual Airflow

0 cfm

AIRFLOW

Primary Damper Position

100 %

DMPPOS

Measured Velocity Pressure

0.000 in. wg

MVP

Supply Air Temperature

0.0 F

SAT

Auto-Calibration

Normal

CAL

Calibration Gain

1.000

CAL_GAIN

501