beautypg.com

Start-up, Perform system, Check-out – Carrier 33ZCFANTRM User Manual

Page 29

background image

29

START-UP

Use the Carrier network communication software to start up

and configure the zone controller.

All set-up and set point configurations are factory-set and

field-adjustable.

Changes can be made using the ComfortWORKS

®

soft-

ware, ComfortVIEW™ software, or Network Service Tool.
The Network Service Tool is a portable interface device that al-
lows the user to change system set-up and set points from a
zone sensor or terminal control module. During start-up, the
Carrier software can also be used to verify communication
with each zone controller.

For specific operating instructions, refer to the literature

provided with the software.

Perform System

Check-Out

1. Check correctness and tightness of all power and com-

munication connections.

2. Check that all air terminals, ductwork, and zone con-

trollers are properly installed and set according to
installation instructions and job requirements.

3. Check that all air duct connections are tight.
4. At the air terminals, check fan and system controls for

proper operation. Verify that actuator screws are prop-
erly tightened.

5. At the air terminals, check electrical system and con-

nections of any optional electric reheat coil. If hot
water reheat is used, check piping and valves against
job drawings.

6. At the air terminals, make sure that all balancing

dampers at box outlets are in the fully open position.

7. If using an air handler with field-installed controls,

make sure controls and sensors have been installed and
wired per manufacturer installation instructions.

8. At air handlers, verify that the motor starter and, if

applicable, the Hand/Off/Auto (HOA) switch are
installed and wired.
NOTE: The HOA switch must be in the Off position.

800

33ZCSENCHG
(SENSOR)

FLOW

1/2” TUBE
3/4” TUBE
1” TUBE

Fig. 24 — Typical Water Valve and Sensor Installation

CCN

1

2

3

CCN

1

2

3

CCN

1

2

3

AIR TERMINAL

UNIT (TYP)

CCN

1

2

3

COMM 2

1

2

3 4

GND

ZC
(TYP)

1000 FT. MAXIMUM

DRAIN WIRE (TYP)

BLK (TYP)

WHT (TYP)

RED (TYP)

BRIDGE
(RECOMMENDED)

LEGEND

Fig. 25 — Communication Bus Wiring

CCN

Carrier Comfort Network

ZC

Zone Controller

This manual is related to the following products: