Table 7 — Occupancy Schedule Information Screen
If a 1 is configured in the corresponding place for a certain
day of the week, the related “Occupied from” and “Occupied
to” times for that period will take effect on that day of the
week. If a 1 is placed in the holiday field the related times will
take effect on a day configured as a holiday. A zero means the
schedule period will not apply to that day.
Period (1-8):
Day of Week:
Range
0 or 1
Default Values
11111111 for period 1,
00000000 for periods 2-8.
Occupied From — This field is used to configure the hour and
minute, in military time, when the mode for the zone controller
becomes occupied.
Period (1-8):
Occupied from:
Units
Hours: Minutes
Range
00:00 to 24:00
Default Value
00:00
Occupied To — This field is used to configure the hour and
minute, in military time, when the occupied mode for the zone
controller becomes unoccupied.
Period (1-8):
Occupied from:
Units
Hours: Minutes
Range
00:00 to 24:00
Default Value
24:00
SET POINT SCREEN — The Set Point screen is used to
modify the zone controller set points. See Table 8.
Occupied Heat — The Occupied Heat set point is used to con-
figure the heating set point for the zone controller during Occu-
pied mode.
Occupied Heat:
Units
F (C)
Range
40.0 to 90.0
Default Value
70.0
Occupied Cool — The Occupied Cool set point is used to con-
figure the cooling set point for the zone controller during Occu-
pied mode.
Occupied Cool:
Units
F (C)
Range
45.0 to 99.9
Default Value
74.0
Unoccupied Heat — The Unoccupied Heat set point is used to
configure the heating set point for the zone controller during
Unoccupied mode.
Unoccupied Heat: Units
F (C)
Range
40.0 to 90.0
Default Value
55.0
Unoccupied Cool — The Unoccupied Cool set point is used to
configure the cooling set point for the zone controller during
Unoccupied mode.
Unoccupied Cool: Units
F (C)
Range
45.0 to 99.9
Default Value
90.0
Occupied High Humidity — The Occupied High Humidity
set point is used to configure the humidity set point for the zone
controller if optional zone humidity control (dehumidification)
is used.
Occupied High Humidity: Units
% Humidity
Range
0.0 to 100.0
Default Value
60.0
Unoccupied High Humidity — The unoccupied high humidi-
ty set point is used to configure the unoccupied humidity set
point for the zone controller if optional zone humidity control
(dehumidification) is used.
Unoccupied
High Humidity:
Units
% humidity
Range
0 to 100
Default Value
100
DESCRIPTION
DEFAULT
POINT NAME
Manual Override Hours
0
OVRD
Period 1: Day of Week
11111111
DOW1
Period 1: Occupied From
00:00
OCC1
Period 1: Occupied To
24:00
UNOCC1
Period 2: Day of Week
00000000
DOW2
Period 2: Occupied From
00:00
OCC2
Period 2: Occupied To
24:00
UNOCC2
Period 3: Day of Week
00000000
DOW3
Period 3: Occupied From
00:00
OCC3
Period 3: Occupied To
24:00
UNOCC3
Period 4: Day of Week
00000000
DOW4
Period 4: Occupied From
00:00
OCC4
Period 4: Occupied To
24:00
UNOCC4
Period 5: Day of Week
00000000
DOW5
Period 5: Occupied From
00:00
OCC5
Period 5: Occupied To
24:00
UNOCC5
Period 6: Day of Week
00000000
DOW6
Period 6: Occupied From
00:00
OCC6
Period 6: Occupied To
24:00
UNOCC6
Period 7: Day of Week
00000000
DOW7
Period 7: Occupied From
00:00
OCC7
Period 7: Occupied To
24:00
UNOCC7
Period 8: Day of Week
00000000
DOW8
Period 8: Occupied From
00:00
OCC8
Period 8: Occupied To
24:00
UNOCC8
1001
→
→