LINKAGE COORDINATOR CONFIGURATION
SCREEN — The Linkage Coordinator Configuration screen
allows the user to set the linkage coordinator configuration set-
tings. See Table 6.
Linkage Master Zone — This decision defines if the zone
controller will function as a Linkage Coordinator (Linkage
Master) for itself and other zones.

If the zone controller is to use a supply air sensor for stand-

alone operation, this configuration must be configured to No
and the number of Zones to 1.

If the zone controller will use its primary air sensor to deter-

mine the air handler mode for a number of zone controllers,
configure this configuration to Yes, input the number of zones,
and leave the air source decisions at the default values of zero.

If this zone controller will communicate linkage informa-

tion with an air source, configure this configuration to Yes. The
number of zones must be configured and the address of the air
source entered.
Linkage
Master Zone:

Range

Yes/No

Default Value

No

Number of Zones — This decision defines the number of zone
controllers (including itself) for the Linkage Coordinator to
scan and include as part of the average temperature, set points,
and occupancy information to the air source. The address of the
zone controller functioning as a Linkage Coordinator must be
larger than the number of zones configured. The zone control-
ler will scan addresses less than its own, including information
for as many zones as are configured. Other zone controller con-
figured as linkage coordinators will also be included, so it is
possible to have zones scanned by more than one linkage coor-
dinator. Therefore care must be taken in addressing to prevent
overlapping systems, unless overlapping systems is necessary.
In large buildings the use of bridges and multiple busses is rec-
ommended to improve communication and provide system
differentiation.
Number of
Zones:

Range

1 to 128

Default Value

1

Air Source Bus and Element Number — The Air Source Bus
and Element Number configurations define the address of the
air source providing conditioned air to the zones controlled by
the linkage coordinator. If the address is left at zero, the Link-
age coordinator will look for a primary air sensor to determine
the equipment mode. If no primary air sensor is installed, or the
sensor fails, the Linkage Coordinator will default the air source
mode to Cooling.
Air Source
Bus Number:

Range

0 to 240

Default Value

0

Air Source
Element Number:

0 to 240

Default Value

0

Static Pressure Reset — Air systems designed with diversity
(airflow required with all zones at maximum cfm exceeds de-
sign capacity of air handler) are capable of providing enough
CFM to all zones on days when conditions meet the demand at
design static. At other times, the air system does not require the
design static to meet the load requirements.

Static pressure reset allows the static pressure set point on

the air source to be reset whenever the system load is reduced
from the design maximum. The zone controller will then moni-
tor damper positions. When the system dampers are modulat-
ing at lower damper positions due to the higher static, the static
pressure will then be reset to a lower value allowing the damp-
ers to open more. This allows the system to automatically make
adjustments to the static pressure and optimize performance of
the fan which will reduce energy consumption.

The linkage coordinator monitors the position of all damp-

ers in its system. When any zone’s maximum damper position
reaches the Reset Maximum Damper Position, the linkage co-
ordinator will reduce the value of the reset variable.

The Maximum Damper Position and Static Pressure Reset

values can be viewed on the Linkage maintenance screen.
NOTE: The static pressure set point configured in the air
source should be the desired maximum (zero reset) static
pressure.

Table 6 — Linkage Coordinator Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

Zone Linkage

Linkage Master Zone

No

MZENA

Number of Zones

1

NSYSTZ

Air Source Bus Number

0

ASBUSN

Air Source Element Number

0

ASELEMN

Static Pressure Reset
Reset Minimum Damper Position

50 %

MINDP

Reset Maximum Damper Position

80 %

MAXDP

Maximum Reset

0.0 in. wg

SPMAX

SP Reset Variable Name

(blank)

SPRVAR

CCN Linkage Data

CCN Variable Name

(blank)

CCNVAR

CCN Function Configuration

3

CCNFUNC

Data Transfer Rate

10 minutes

DATARATE

CCN Output Point

(blank)

CCNOUTP

Destination Bus Number

0

DESTBUSN

Destination Element Number

0

DESTELEN

Temperature Sensor Grouping

Temperature Sensor Mode

1

BRD_RECV

Temperature Sensor Configuration

1

SENSCFG

Broadcast Device ID

1

BRDDEVID

801