32

SUPPLY AIR TEMPERATURE — Temperature of the air
leaving the zone controller downstream of any ducted heat
source. Measured by a 10 k

Ω thermistor (Type III). This tem-

perature is used to control the maximum discharge air to the
space when local heat is active. The sensor is not required or
recommended for cooling only terminals. If supply air temper-
ature display is required by specification, on a cooling only
box, a heat type other than zero must be configured. This
will have no adverse affect on the operation of a cooling only
terminal.
Supply
Air Temperature: Display Units

F (C)

Default Value

0.0

Display Range

-40.0 to 245.0

Network Access Read/Write

LOCAL HEATING CAPACITY — When local heat at the
terminal is enabled the percent of heat being delivered is deter-
mined by the following formula for modulating (floating point)
type heat:

% Capacity = [(SAT - SPT)/(Maximum Duct Temp – SPT )]
The percent of heat delivered is determined by the follow-

ing for two-position hot water or staged electric heat:

% Output Capacity = (# of active stages/Total stages) * 100

Local Heating
Capacity:

Display Units

% output capacity

Default Value

0

Display range

0 to 100

Network Access Read only

TERMINAL FAN — The commanded output for the terminal
fan on a fan powered terminal.
Terminal Fan:

Display Units

Discrete ASCII

Default Value

Off

Display Range

Off/On

Network Access Read/Write

RELATIVE HUMIDITY — Space Relative Humidity read-
ing from the optional relative humidity sensor. Used by Hu-
midity control function if configured.
Relative
Humidity:

Display Units

% RH

Default Value

0

Display Range

0 to 100

Network Access Read/Write

AIR QUALITY — Indoor air quality reading from a CO

2

sen-

sor installed in the space. Used by Air Quality control function
if configured.

Air Quality (ppm):Display units

None shown (parts per
million implied)

Default Value

0

Display range

0 to 5000

Network Access Read/Write

SECONDARY AIRFLOW — Airflow reading from the sec-
ondary pressure transducer, supplied with the secondary actua-
tor, intended for dual duct and pressure control applications.
Secondary
Airflow:

Display Units

cfm

Default Value

0

Display Range

0 to 9999

Network Access Read/Write

PRIMARY AIR TEMPERATURE — Primary air tempera-
ture from sensor (10 k

Ω, Type III), located in main trunk of

ductwork for supply air provided by the air-handling equip-
ment. Used for linkage coordination.
Primary Air
Temperature:

Display Units

F (C)

Default Value

0.0

Display Range

-40.0 to 245.0

Network Access Read/Write

HEAT ENA BLE/D IS ABLE — Provides enable/disable
function for local heat at the terminal. When enabled the Local
heat capacity function will run to operate the terminal heat.
Heat Display:

Display Units

Discrete ASCII

Default Value

Dsable

Display Range

Dsabe/Enable

Network Access Read/Write

Modify Controller Configuration —

In Service

Tool software, select the desired zone controller and access the
Modify Controller Configuration Menu screen. This configura-
tion screen is also displayed under CONFIGURE when using
ComfortWORKS

®

and ComfortVIEW™ software.

The Modify Controller Configuration Menu screen is used

to access the Alarm Limit Configuration screen, Controller
Identification screen, Holiday Configuration screen, Linkage
Coordinator Configuration screen, Occupancy Configuration
screen, and Set Point screen.
ALARM LIMIT CONFIGURATION SCREEN — The
Alarm Limit Configuration screen is used to configure the
alarm settings for the zone controller. See Table 5.

Table 5 — Alarm Limit Configuration Screen

DESCRIPTION

DEFAULT

POINT NAME

Alarm Routing Control

00000000

ROUTING

Re-Alarm Time

0

RETIME

SPT Occupied Hysteresis

5.0 F

SPTHYS

Unoccupied SPT
Low Limit
High Limit

40 F
99 F

LOWLIM

HIGHLIM

Occupied RH
Low Limit
High Limit

10 %
99 %

LOWLIM

HIGHLIM

Unoccupied RH
Low Limit
High Limit

0 %

100 %

LOWLIM

HIGHLIM

Air Quality
Low Limit
High limit

250 ppm

1200 ppm

LOWLIM

HIGHLIM

High Velocity Pressure

1.2 in. wg

HIGHVP

801